'14 • KX-SM-204
Code
No.
Remarks
Contents of display
Data display
range
Minimum
unit
C94
C98
P01
P02
P03
P04
P05
P06
P14
P15
P16
0~80
0.00~9.99
0~12
0~12
0~12
0~12
0.01
—
1
—
30
—
1
1
1
1
1
1
Switching to operation priority
Outdoor fan snow protection control
Outdoor fan snow protection control ON time
setting
Silent mode setting
CNZ1 function assignment
CNS1 function assignment
CNS2 function assignment
CNG1 function assignment
CNG2 function assignment
Changes to 10, 30, 60, 90 … 600.
Factory setting: 0 (External operation input)
Factory setting: 1 (Demand input)
Factory setting: 2 (Forced cooling/heating input)
Factory setting: 3 (Silent mode input)
0: (Factory default)
0, 1
0: (Factory default)
0, 1
0: (Factory default)
0, 1
0: (Factory default)
0, 1
0: (Factory default)
0, 1
0: (Factory default)
0, 1, 2, 3
0: (Factory default)
0, 1, 2, 3
Program sub-version
Program POL version
C97
C99
Many steps demand setting (1st step demand)
Auto send display
Auto back up capable time
1h
0~991
—
—
0 : Invalid
1 : Valid
30: (Factory default)
10,30~600(sec)
080: (Factory default)
000,040,060,080
080: (Factory default)
000,040,060,080
080: (Factory default)
000,040,060,080
0: (Factory default)
0 ~ 3
0: (Factory default)
0 ~ 9
P07
P08
P09
P10
Many steps demand setting. (2nd step demand)
Many steps demand setting. (3nd step demand)
Multi-system energy save control II
1
—
—
-
22
-
P17
P18
P19
P30
P31
P32
P33
P34
0, 1
—
—
1
1
1
—
Superlink communication status
Start automatic address setting
Input stating indoor address
Input the number of connected indoor units
Polarity definition
<New Superlink setting>
0: Current Superlink
1: New Superlink
0: Automatic address setting standby
1: Automatic address setting start
0: Network polarity not defined
1: Network polarity defined
0: (Factory default)
0, 1
0: (Factory default)
1~127
0: (Factory default)
1~24(*)
Specify the starting indoor address connected in one refrigerant system
for automatic address setting.
Specify the number of indoor units connected in one refrigerant system
for automatic address setting.
(*) Maximum connectable number of indoor units for each outdoor unit
After changing mode from operation prohibition
mode
Mode unmatched indoor unit setting in forced mode
Pump-down operation by external input
1
1
1
P69
Multi-system energy save control I