'14 • KX-SM-204
1.2 Operation control function by the wired remote control
Cooling
Fan
Dry
Heating
(1) Switching sequence of the operation mode switches of remote control
(a) Tap the change operation mode button on the TOP screen.
(b) When the change operation mode screen is displayed, tap the button of desired mode.
(c) When the operation mode is selected, the display returns to the TOP screen.
Icons displayed have the following meanings.
Notes(1) Operation modes which cannot be selected depending on combinations of IU and
OU are not displayed.
Notes
(2) When the Auto is selected, the cooling and heating switching operation is
performed automatically according to indoor and outdoor temperatures.
(2) CPU reset
Reset CPU from the remote control as follows.
(3) Power failure compensation function (Electric power supply failure)
Enable the Auto-restart function from the remote control as follows.
①
Tap the Menu button
on the TOP screen.
②,③
Main menu screen is displayed.
Tap the “Service & Maintenance” on the menu screen.
④
Display the service
password input screen.
Enter the service password
(4-digit number).
①
TOP screen
②
Menu screen 1
③
Menu screen 3
④
Service password input
①
Tap the Menu button
on the TOP screen.
②,③
Main menu screen is displayed.
Tap the “Service & Maintenance” on the menu screen.
④
Display the service
password input screen.
Enter the service password
(4-digit number).
①
TOP screen
②
Menu screen 1
③
Menu screen 3
④
Service password input
⑤
Service & maintenance menu 1
⑥
Service & maintenance menu 2
⑤,⑥
Service & maintenance menus are displayed.
⑦
Special settings
⑦
Special settings
CPU reset : Microcomputers of IU
and OU connected are reset
(State of restoration after
power failure).
⑧
CPU reset
All microcomputers on the R/C operated,
other R/Cs, IUs and OUs are reset (State
of restoration after power failure).
Tap [Yes] to reset CPU
⑤,⑥,⑦
Display the R/C setting menu screens.
⑤
R/C setting menu 1
⑥
R/C setting menu 2
⑦
R/C setting menu 3
⑱
Auto-restart
Enable : It returns to the state be fore the supply
power failure as soon as the power is
restored (After the end of the primary
control at the power on).
Disable : It stops after the restoration of power
supply, regardless the state of operation
before the power failure.
⑱
Auto-restart
Set the state of operation to be started when the
power supply is restored after a power failure.
⑧
CPU reset
CPU reset
Restart after reset
If OK, tap[Set.]
Model RC-EX1A