82
–
Error code
Remote control:
7-segment display: –
LED
Green
Red
Indoor
Outdoor
Content
'14 • KX-SM-204
WAIT
WAIT
(4)
Keeps flashing
Stays OFF
Keeps flashing Keeps flashing
1. Applicable model
5. Troubleshooting
All models
(In case that is kept
on displaying on the remote
control for more than 2 minutes
after power ON.)
Diagnosis
Countermeasure
NO
Does
outdoor green LED keep
flashing?
is kept on
displaying on the remote
control for more than 2
minutes after power ON.
Does
indoor green LED keep
flashing?
Does
outdoor red LED flash
2 times?
Are
the wires between indoor
and outdoor units
connected properly ?
Is
AC380-415V detected
between L1-L2, L2-L3, L3-L1
respectively at outdoor
terminal block?
Is
AC220-240V detected
between L-N at indoor
terminal block?
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
A
Refer next page.
WAIT
Indoor control PCB
anomaly
Replace it.
Indoor control PCB
anomaly
Replace it.
Remote control anomaly
Replace it.
Breakage of wires for
remote control
Replace it.
Correct the connecting
wires between indoor and
outdoor units.
Outdoor control PCB
anomaly
Replace it.
Breakage of connecting
wire
Noise.
Indoor control PCB
anomaly
Replace it.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Fuse blown
• Noise filter anomaly
• Anomalous connection of
wire between PCBs
• Indoor control PCB anomaly
• Remote control anomaly
• Breakage of connecting wires
of remote control
• Outdoor control PCB anomaly
Note:
WAIT