'14 • KX-SM-204
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E2
–
Duplicated indoor unit address
Keeps flashing Keeps flashing
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the number of
connected indoor units up
to 128 units?
Is the different
address No. assigned to each
indoor unit?
Is E2 displayed?
Reset the power supply and restart.
Caution:
Unless the power
supply is reset,
addresses will not
be confirmed.
YES
NO
YES
NO
YES
NO
Review number of
connected units.
Correct indoor unit address
setting.
Implement test run.
Replace indoor control
PCB. *
* Before replacement,
confirm whether the
rotary switch for address
setting is not damaged.
(It was experienced that
No. 5 on rotary switch
was not recognized.)
2. Error detection method
More than 129 indoor units are
connected in the same Superlink
system.
Duplicated indoor unit address
3. Condition of error displayed
Same as above
4. Presumable cause
• Number of connected indoor
units exceeds the limitation.
• Duplicated indoor unit
address
• Indoor control PCB anomaly
Note: