'14 • KX-SM-204
–
96
–
E16
–
Indoor fan motor anomaly
(FDT, FDTC, FDTW, FDTS, FDU,
FDUM, FDK, FDUT71, FDFW series)
Keeps flashing 1-time flash
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
FDT, FDTC, FDTW, FDTS,
FDU, FDUM, FDK, FDUT71,
FDFW series only
Diagnosis
Countermeasure
NO
YES
YES
Does any
foreign matter intervene
in rotational area of fan
propeller?
Is DC280V
detected between
�
-
�
(
�
-
�
) of
fan motor connector
CNM?
(1)(2)
Does it become normal?
Is the fuse F3 (F4) or F202 blown?
Does the fan
rotate smoothly when turned
by hand?
YES
NO
NO
NO
YES
NO
YES
Reset the power supply and restart.
Note (1)
�
(
�
) is GND.
(2) Valve in ( ) are for the model
FDFW and FDK.
Remove foreign matter.
Replace the fan motor.
Check power supply
voltage.
Replace fan motor and
power PCB.
Replace fan motor. (If
the anomaly persists after
replacing the fan motor,
replace the indoor control
PCB.)
Malfunction by temporary
noise.
2. Error detection method
Detected by revolution speed of
indoor fan motor.
3. Condition of error displayed
When actual revolution speed of
indoor fan motor drops to lower
than 200min
-1
for 30 seconds
continuously, the compressor
and the indoor fan motor stop.
After 2-seconds delay, fan
motor starts again automatically,
but if this anomaly occurs 4
times within 60 minutes after
the initial detection.
4. Presumable cause
• Indoor fan motor anomaly
• Foreign matter at rotational
area of fan propeller
• Fan motor anomaly
• Dust on control PCB
• Blown fuse
• External noise, surge
Note:
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content