'19 • PAC-SM-309
-
99
-
E1
Remote control
communication circuit error
Keeps flashing Stays OFF
Keeps flashing Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is it possible to
reset normally by the
power reset?
Does the drain
pump restart automatically
1 minute later?
YES
YES
NO
Note (1) Only indoor unit
with drain pump
Turn SW7-1 to OFF.
➝
ON
Remove the wire
③
connecting
between indoor/outdoor units.
Connect the wire
③
connecting
between indoor/outdoor units.
Power source reset
NO
(
1
)
Malfunction by noise
Check peripheral
environment.
Defective indoor unit control
PCB
➞
Replace.
Move to E5.
(Communication error
during operation) check.
2. Error detection method
When normal communication
between the remote control and
the indoor unit is interrupted
for more than 2 minutes.
(Detectable only with the
remote control)
3. Condition of error displayed
Same as above
4. Presumable cause
• Defective communication
circuit between remote
control-indoor unit
• Noise
• Defective remote control
• Faulty indoor unit control PCB
Note:
If the indoor unit cannot communicate normally with the remote control for 180 seconds, the indoor unit PCB starts to reset
automatically.
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
Summary of Contents for FDC100VNA-W
Page 70: ... 19 PAC SM 309 69 LED2 Red LED1 Green ...
Page 72: ... 19 PAC SM 309 71 ...
Page 74: ... 19 PAC SM 309 73 LED2 Red LED1 Green ...
Page 76: ... 19 PAC SM 309 75 ...
Page 183: ... 19 PAC SM 309 182 1 e SRK series PHA012D402 ...
Page 184: ... 19 PAC SM 309 183 Screw ...
Page 185: ... 19 PAC SM 309 184 3 PHA012D402 ...
Page 186: ... 19 PAC SM 309 185 4 PHA012D402 ...