'19 • PAC-SM-309
-
116
-
Error code
Remote control:
LED
Green
Red
1-time flash
Keeps flashing
Stays OFF
Keeps flashing
Content
Indoor unit
control PCB
Outdoor unit
control PCB
Outdoor air temperature
sensor anomaly
E38
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is
the outdoor air
temperature sensor connector
connected properly?
YES
Is the
characteristics of the
outdoor air temperature
sensor
OK?
NO
For the characteristics of outdoor air
temperature sensor, see the following graph.
YES
0
5
10
15
20
25
30
35
0
10
20
30
40
50
NO
Temperature-resistance characteristics
Temperature sensor resistance (k
Ω
)
Temperature (°C)
(Broken wire)
(Short-circuit)
Correct connector.
Defective outdoor
air temperature
sensor
➞
Replace.
Defective outdoor unit main
PCB
➞
Replace.
(Defective outdoor air
temperature sensor
input circuit)
2. Error detection method
Detection of anomalously low
temperature (resistance) on
outdoor air temperature
sensor
3. Condition of error displayed
•
When the temperature sensor
detects -45°C or lower for 5
seconds continuously within 2
minutes to 2 minutes 20 seconds
after the compressor ON, the
compressor stops. After 3-minute
delay, the compressor starts again
automatically, but if this anomalous
temperature is detected 3 times
within 40 minutes.
•
When -45°C or lower is detected for
5 seconds continuously within 20
second after compressor ON.
4. Presumable cause
• Defective outdoor unit main
PCB
• Broken sensor harness or
temperature sensing section
(Check molding.)
• Disconnected wire connection
(connector)
Note:
Summary of Contents for FDC100VNA-W
Page 70: ... 19 PAC SM 309 69 LED2 Red LED1 Green ...
Page 72: ... 19 PAC SM 309 71 ...
Page 74: ... 19 PAC SM 309 73 LED2 Red LED1 Green ...
Page 76: ... 19 PAC SM 309 75 ...
Page 183: ... 19 PAC SM 309 182 1 e SRK series PHA012D402 ...
Page 184: ... 19 PAC SM 309 183 Screw ...
Page 185: ... 19 PAC SM 309 184 3 PHA012D402 ...
Page 186: ... 19 PAC SM 309 185 4 PHA012D402 ...