'19 • PAC-SM-309
-
121
-
1. Applicable model
5. Troubleshooting
Models FDC
-W
Diagnosis
Countermeasure
YES
NO
NO
Is the
power s
voltage OK?
NO
Does it become nomal?
Change the control PCB (P B1)
Are wires
connected properly
between the reactor PCB
(P 7) and the control
PCB (P B1) ?
YES
Check power source.
Correct wires.
Change the reactor PCB
(P B7) and the connection
wire between the reactor
PCB (P B7) and the
control PCB (P B1).
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Defective main PCB
Note:
In order to avoid an unexpected
trouble, if the protective circuit
defect unexpected voltage,
current and movement of the
power element, it makes the
compressor stopping.
• If the
anomaly occurs,
it makes the compressor
stopping.
• After 3-minute delay, the
compressor restarts
f this anomaly occurs 4
times within 30 minutes or
continues for 15 minutes
contin ously.
Error code
Remote control:
LED
Green
Red
1-time flash
Keeps flashing
Stays OFF
Keeps flashing
Content
E47
PCB A/F module anomaly
(Models FDC100-140VNA-W
only)
• Defective reactor PCB
ource
Indoor unit
control PCB
Outdoor unit
control PCB
Summary of Contents for FDC100VNA-W
Page 70: ... 19 PAC SM 309 69 LED2 Red LED1 Green ...
Page 72: ... 19 PAC SM 309 71 ...
Page 74: ... 19 PAC SM 309 73 LED2 Red LED1 Green ...
Page 76: ... 19 PAC SM 309 75 ...
Page 183: ... 19 PAC SM 309 182 1 e SRK series PHA012D402 ...
Page 184: ... 19 PAC SM 309 183 Screw ...
Page 185: ... 19 PAC SM 309 184 3 PHA012D402 ...
Page 186: ... 19 PAC SM 309 185 4 PHA012D402 ...