'19 • PAC-SM-309
-
122
-
Error code
Remote control:
LED
Green
Red
1-time flash
Keeps flashing
Stays OFF
Keeps flashing
Content
Indoor unit
control PCB
Outdoor unit
control PCB
E48
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
YES
NO
Does any foreign
material intervene in rotational area
of fan propeller?
NO
Does the
fan rotate smoothly when turned
by hand?
NO
Is DC280V
detected between (CNFAN
➀
(red)-
➃
(blue)) of fan motor
connector?
Is F2 fuse blown?
Is normal state restored?
Is DC15V detected
between (CNFAN
⑤
-
③
) when the
connector for FMo is removed from
outdoor unit main PCB?
YES
YES
YES
NO
YES
NO
NO
YES
Power source reset
Remove foreign material.
Replace fan motor.
If resistance between
➀
(Vm):red -
➃
(GND):blue is
detected 1k
Ω
or lower, it is
faulty.
Check power source
voltage.
Replace faulty fan motor
and outdoor unit main PCB.
Replace outdoor unit main
PCB.
Replace fan motor (If
anomaly persists after
replacing fan motor, replace
outdoor unit main PCB.)
Malfunction by temporary
noise
2. Error detection method
Detected by rotation speed of
outdoor fan motor
3. Condition of error displayed
When actual rotation speed
of outdoor fan motor (FMo1)
drops to 100min
-1
or lower
for 30 minutes continuously,
the compressor and the
outdoor fan motor stop. After
3-minute delay, it starts again
automatically, but if this
anomaly occurs 5 times within
60 minutes after the initial
detection.
4. Presumable cause
• Defective outdoor unit main
PCB
• Foreign material at rotational
area of fan propeller
• Defective fan motor
• Dust on outdoor unit main PCB
• Blow fuse
• External noise, surge
Note: When E48 error occurs, in almost cases F2 fuse (4A) on the outdoor unit main PCB is blown. There are a lot of cases that fuse is blown and
E48 occurs due to defective fan motor. And even though only the outdoor unit main PCB ( or fuse) is replaced, another trouble (*1) could
occur. Therefore when fuse is blown, check whether the fan motor is OK or not.
After confirming the fan motor normal, check by power ON. (Don't power ON without confirming the fan motor normal.)
*1 The error which does not seem to relate E48 may occur like as “
WAIT
”, Stay OFF of LED on outdoor unit main PCB, inverter
communication error (E45) and etc.
Outdoor fan motor anomaly
Summary of Contents for FDC100VNA-W
Page 70: ... 19 PAC SM 309 69 LED2 Red LED1 Green ...
Page 72: ... 19 PAC SM 309 71 ...
Page 74: ... 19 PAC SM 309 73 LED2 Red LED1 Green ...
Page 76: ... 19 PAC SM 309 75 ...
Page 183: ... 19 PAC SM 309 182 1 e SRK series PHA012D402 ...
Page 184: ... 19 PAC SM 309 183 Screw ...
Page 185: ... 19 PAC SM 309 184 3 PHA012D402 ...
Page 186: ... 19 PAC SM 309 185 4 PHA012D402 ...