'19 • PAC-SM-309
-
129
-
Error code
Remote control:
LED
Green
Red
5-time flash
Keeps flashing
Stays OFF
Keeps flashing
Content
Indoor unit
control PCB
Outdoor unit
control PCB
E59
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
pressure equalized
at starting OK?
Is the
insulation resistance and
resistance between terminals(1)
of compressor
OK?
In case that the compressor
does not start at all and no
sound or vibration exists
Is
power source voltage
OK?
NO
NO
For
FDC100-140VNA-W
For
FDC100-140VSA-W YES
Is DC15V
detected after disconnecting
outdoor fan motor?
YES
Replace outdoor unit main PCB
Can compressor startup?
YES
NO
NO
NO
YES
YES
To next page
0.448
Ω
or more at 20°C (Models FDC100-140VNA-W)
1.044
Ω
or more at 20°C (Models FDC100-140VSA-W)
(1)
Check the power source
voltage and correct it.
Replace outdoor fan motor.
OK
Check refrigerant amount
and refrigerant circuit.
Replace compressor.
2. Error detection method
When it fails to change over to
the operation for rotor position
detection of compressor motor
3. Condition of error displayed
If the compressor fails to startup
for 20 times (10 patterns x2
times) continuously.
4. Presumable cause
• Outdoor fan motor anomaly
• Outdoor unit main PCB
anomaly
• Anomalous power source
voltage
• Insufficient or excessive
refrigerant amount
• Faulty component for
refrigerant circuit
• Compressor anomaly
(Motor or bearing)
Note: Insulation resistance
•
The unit is left for long period without power source or soon after installation, insulation resistance may decrease to several MΩ or lower due to the liquid refrigerant
migrated in the refrigerant oil in compressor. If the electric leakage breaker is activated due to low insulation resistance, check followings.
➀
Check whether the insulation resistance can recover or not, after 6 hours has passed since power ON.
(By energize the crankcase heater, liquid refrigerant migrated in the refrigerant oil in compressor can be evaporated)
➁
Check whether the electric leakage breaker conforms to high-harmonic specifications
(As inverter PAC units has inverter, in order to prevent from improper operation, be sure to use the breaker of high-harmonic type)
Compressor startup failure (1/2)
Summary of Contents for FDC100VNA-W
Page 70: ... 19 PAC SM 309 69 LED2 Red LED1 Green ...
Page 72: ... 19 PAC SM 309 71 ...
Page 74: ... 19 PAC SM 309 73 LED2 Red LED1 Green ...
Page 76: ... 19 PAC SM 309 75 ...
Page 183: ... 19 PAC SM 309 182 1 e SRK series PHA012D402 ...
Page 184: ... 19 PAC SM 309 183 Screw ...
Page 185: ... 19 PAC SM 309 184 3 PHA012D402 ...
Page 186: ... 19 PAC SM 309 185 4 PHA012D402 ...