'19 • PAC-SM-309
-
130
-
Error code
Remote control:
LED
Green
Red
5-time flash
Keeps flashing
Stays OFF
Keeps flashing
Content
Indoor unit
control PCB
Outdoor unit
control PCB
E59
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
Is the
power transistor
module OK?
(Outdoor unit main PCB anomaly)
NO
Is the
inverter output OK?
(Check by inverter
checker)
Does it start?
NO
YES
YES
YES
Note(1) Several times restarting
may recover it, because
liquid refrigerant migrated
in the compressor could
be discharged from the
compressor.
After power OFF, turn SW6-4 of
outdoor unit main PCB ON and
connect the outdoor unit main
checker. Then power ON again.
Try to restart several times
From previous page
Replace outdoor unit main
PCB.
Replace outdoor unit main
PCB.
Replace compressor.
2. Error detection method
When it fails to change over to
the operation for rotor position
detection of compressor motor
3. Condition of error displayed
If the compressor fails to startup
for 20 times (10 patterns x2
times) continuously.
4. Presumable cause
• Outdoor fan motor anomaly
• Outdoor unit main PCB
anomaly
• Anomalous power source
voltage
• Insufficient or excessive
refrigerant amount
• Faulty component for
refrigerant circuit
• Compressor anomaly
(Motor or bearing)
Note:
Compressor startup failure (2/2)
Summary of Contents for FDC100VNA-W
Page 70: ... 19 PAC SM 309 69 LED2 Red LED1 Green ...
Page 72: ... 19 PAC SM 309 71 ...
Page 74: ... 19 PAC SM 309 73 LED2 Red LED1 Green ...
Page 76: ... 19 PAC SM 309 75 ...
Page 183: ... 19 PAC SM 309 182 1 e SRK series PHA012D402 ...
Page 184: ... 19 PAC SM 309 183 Screw ...
Page 185: ... 19 PAC SM 309 184 3 PHA012D402 ...
Page 186: ... 19 PAC SM 309 185 4 PHA012D402 ...