'19 • PAC-SM-309
-
141
-
Error code
Remote control:
Indoor
display
RUN light TIMER light
Green LED Red LED
Outdoor unit
control PCB
Content
INSPECT I/U
INSPECT I/U
(When 1 or 2 remote controls are connected)
–
–
Keeps flashing 2-time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Are 2 units
of remote control
connected?
Is it set
at the slave remote
control?
⑴,
⑵
Note (1) Use SW1 to set at
master or slave.
Note (2)
“Slave” is displayed
on the remote
control LCD.
⑵
Does it
become normal?
Do more than
one interface kit have the
same address?
Are remote
control wires laid
along high voltage
wires?
NO
YES
YES
NO
NO
NO
NO
YES
YES
Set one remote control
for “Master” and the other
for “Slave”
Is approx.
DC20V detected between
➁
-
➂
on the interface kit terminal
block?
Is approx.
DC20V detected between
➁
-
➂
on the remote control terminal
block?
YES
YES
NO
NO
Set SW1 on remote control
PCB at “Master”.
Set address again. (SW3 on
interface kit PCB)
Separate remote control
wires from high voltage
wires.
Defective interface kit
PCB
➞
Replace.
Broken connecting wire
➞
Correct.
Defective remote control
PCB
➞
Replace.
2. Error detection method
Communication between indoor
unit and remote control is
disabled for more than 30
minutes after the power on.
3. Condition of error displayed
Same as above
4. Presumable cause
• Improper setting
• Surrounding environment
• Defective remote control
communication circuit
• Faulty interface kit PCB
Note:
If any error is detected 30 minutes after displaying “
WAIT
” on the remote control, the display changes to
“INSPECT I/U”.
Summary of Contents for FDC100VNA-W
Page 70: ... 19 PAC SM 309 69 LED2 Red LED1 Green ...
Page 72: ... 19 PAC SM 309 71 ...
Page 74: ... 19 PAC SM 309 73 LED2 Red LED1 Green ...
Page 76: ... 19 PAC SM 309 75 ...
Page 183: ... 19 PAC SM 309 182 1 e SRK series PHA012D402 ...
Page 184: ... 19 PAC SM 309 183 Screw ...
Page 185: ... 19 PAC SM 309 184 3 PHA012D402 ...
Page 186: ... 19 PAC SM 309 185 4 PHA012D402 ...