'19 • PAC-SM-309
-
149
-
Error code
Remote control:
Indoor
display
RUN light TIMER light
Green LED Red LED
Outdoor unit
control PCB
Content
Note(1) Value in ( ) are the Th2
2
.
E6
Indoor heat exchanger
temperature sensor anomaly
1(3)-time flash
(1)
ON
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
NO
YES
Is the
connection of indoor heat
exchanger temperature sensor
connector OK?
Are
characteristics of indoor
heat exchanger temperature
sensor OK?
YES
Temperature-resistance characteristic
Temperature sensor resistance (k
Ω
)
Temperature (°C)
15
10
5
0
10
30
40
20
50
(Broken wire)
(Short-circuit)
5k
Ω
at 25
°C
Correct.
➞
Insert connector
securely.
Defective indoor heat
exchanger temperature
sensor
➞
Replace.
Defective indoor unit
control PCB
➞
Replace.
(Defective indoor unit heat
exchanger temperature
sensor input circuit)
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected on the indoor heat
exchanger sensor (Th2
1
, Th2
2
).
3. Condition of error displayed
• When the temperature sensor
detects -28°C or lower for 15
seconds continuously, the
compressor stops. After 3-
minutes delay, the compressor
starts again automatically,
but if this error occurs again
within 60 minutes after the
initial detection.
4. Presumable cause
• Defective indoor heat
exchanger sensor connector
• Indoor heat exchanger
temperature sensor anomaly
• Faulty indoor unit control PCB
Note:
Summary of Contents for FDC100VNA-W
Page 70: ... 19 PAC SM 309 69 LED2 Red LED1 Green ...
Page 72: ... 19 PAC SM 309 71 ...
Page 74: ... 19 PAC SM 309 73 LED2 Red LED1 Green ...
Page 76: ... 19 PAC SM 309 75 ...
Page 183: ... 19 PAC SM 309 182 1 e SRK series PHA012D402 ...
Page 184: ... 19 PAC SM 309 183 Screw ...
Page 185: ... 19 PAC SM 309 184 3 PHA012D402 ...
Page 186: ... 19 PAC SM 309 185 4 PHA012D402 ...