'19 • PAC-SM-309
-
150
-
Error code
Remote control:
Indoor
display
RUN light TIMER light
Green LED Red LED
Outdoor unit
control PCB
Content
None
Room temperature
sensor anomaly
2-time flash
ON
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
NO
YES
Is the
connection of room
temperature sensor
connector OK?
Are the
characteristics of room
temperature sensor
OK?
YES
15
10
5
0
10
30
40
20
50
Temperature-resistance characteristic
Temperature sensor resistance (k
Ω
)
Temperature (°C)
5k
Ω
at 25
°C
(Broken wire)
(Short-circuit)
Correct.
➞
Connect
connector.
Defective room temperature
sensor
➞
Replace.
Defective indoor unit
control PCB
➞
Replace.
(Defective room
temperature sensor input
circuit)
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected by indoor room
temperature sensor (Th1)
3. Condition of error displayed
•
When the temperature sensor
detects -45°C or lower for 15
seconds continuously, the
compressor stops. After 3-minute
delay, the compressor starts again
automatically, but if this error
occurs again within 60 minutes
after the initial detection.
4. Presumable cause
• Defective room temperature
sensor connector
• Defective room temperature
sensor
• Faulty indoor unit control PCB
Note:
Summary of Contents for FDC100VNA-W
Page 70: ... 19 PAC SM 309 69 LED2 Red LED1 Green ...
Page 72: ... 19 PAC SM 309 71 ...
Page 74: ... 19 PAC SM 309 73 LED2 Red LED1 Green ...
Page 76: ... 19 PAC SM 309 75 ...
Page 183: ... 19 PAC SM 309 182 1 e SRK series PHA012D402 ...
Page 184: ... 19 PAC SM 309 183 Screw ...
Page 185: ... 19 PAC SM 309 184 3 PHA012D402 ...
Page 186: ... 19 PAC SM 309 185 4 PHA012D402 ...