'19 • PAC-SM-309
-
153
-
Error code
Remote control:
Indoor
display
RUN light TIMER light
Green LED Red LED
Outdoor unit
control PCB
Content
E14
Communication error
between master and slave indoor units
–
–
Keeps flashing Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is it
OK the unit
address setting for master
and slave interface
kit?
NO
YES
Isn’t
the remote
control wiring between
interface kit
defective?
YES
NO
Isn’t
the interface
kit wiring between
indoor units
defective?
Is it
restored by resetting the
power source?
Note (1) Set DIP switches SW3-1 and SW3-2 as shown in the following table.
(Factory default setting – “Master”)
Master
Slave1
Slave2
SW3-1
OFF
OFF
ON
SW3-2
OFF
ON
OFF
DIP
switch
Interface kit
YES
NO
NO
YES
Correct unit address setting.
Correct wiring.
Correct wiring.
Defective indoor unit
control PCB Replace.
• Malfunction by noise
• Check surrounding
environment.
2. Error detection method
When communication error
between master and slave indoor
units occurs
3. Condition of error displayed
Same as above
4. Presumable cause
• Unit address setting error
• Broken remote control wire
• Defective remote control wire
connection
• Broken interface kit wire
• Defective interface kit wire
connection
• Defective indoor unit control
PCB
Note:
Summary of Contents for FDC100VNA-W
Page 70: ... 19 PAC SM 309 69 LED2 Red LED1 Green ...
Page 72: ... 19 PAC SM 309 71 ...
Page 74: ... 19 PAC SM 309 73 LED2 Red LED1 Green ...
Page 76: ... 19 PAC SM 309 75 ...
Page 183: ... 19 PAC SM 309 182 1 e SRK series PHA012D402 ...
Page 184: ... 19 PAC SM 309 183 Screw ...
Page 185: ... 19 PAC SM 309 184 3 PHA012D402 ...
Page 186: ... 19 PAC SM 309 185 4 PHA012D402 ...