'19 • PAC-SM-309
-
163
-
E42
Current cut (2/2)
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
After
resetting power for
several times does it
become normal?
NO
YES
Temporary noise may cause of anomaly.
If noise source can be found, take countermeasure.
Is the
checked result of power
transistor module
OK?
NO
• Is the space for installation of indoor and/or outdoor unit enough?
• Is there any short circuit of air on indoor and/or outdoor unit?
• At cooling, does the outdoor fan motor run?
Are the service valves fully opened?
Is the filter clogged?
• At heating, does the indoor fan motor run?
Are the service valves fully opened?
Is the filter clogged?
• Is there any liquid flooding?
Is the superheat within normal range?
Is the low pressure sensor and suction pipe temperature
sensor normal?
• Is there any anoumalous sound on the compressor?
YES
YES
From previous page
Defective outdoor unit
main PCB
➞
Replace.
Defective outdoor unit
main PCB
➞
Replace.
2. Error detection method
In order to prevent from
overcurrent of inverter,
if the current exceeds the
specifications, it makes the
compressor stopping.
3. Condition of error displayed
•
If the output current of inveter
exceeds the specifications,
it makes the compressor
stopping.
•
After 3-minute delay, the
compressor restarts, but if this
amonaly occurs 4 times within
30 minute after the initial
detection.
4. Presumable cause
• Defective outdoor unit main
PCB
• Faulty power source
• Insufficient refrigerant amount
• Faulty compressor
• Faulty power transistor
module
Note:
Error code
Remote control:
Content
1-time flash
Keeps flashing
1-time flash
ON
Indoor display
RUN light
TIMER light
Green LED
Red LED
Outdoor unit
control PCB
Summary of Contents for FDC100VNA-W
Page 70: ... 19 PAC SM 309 69 LED2 Red LED1 Green ...
Page 72: ... 19 PAC SM 309 71 ...
Page 74: ... 19 PAC SM 309 73 LED2 Red LED1 Green ...
Page 76: ... 19 PAC SM 309 75 ...
Page 183: ... 19 PAC SM 309 182 1 e SRK series PHA012D402 ...
Page 184: ... 19 PAC SM 309 183 Screw ...
Page 185: ... 19 PAC SM 309 184 3 PHA012D402 ...
Page 186: ... 19 PAC SM 309 185 4 PHA012D402 ...