'19 • PAC-SM-309
-
169
-
E53
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
YES
NO
Are the
characteristics of suction pipe
temperature sensor OK?
YES
Is the connection
of suction pipe temperature sensor
connector OK?
NO
Temperature-resistance characteristics
Temperature sensor resistance (k
Ω
)
Temperature (°C)
15
10
5
0
10
30
40
20
50
5k
Ω
at 25°C
(Broken wire)
(Short-circuit)
Correct connection of
suction pipe temperature
sensor connector.
Defective suction pipe
temperature sensor
➞
Replace.
Defective outdoor unit
main PCB
➞
Replace.
(Defective suction pipe
temperature sensor input
circuit)
2. Error detection method
When the suction pipe
temperature sensor detects
anomalously low temperature
3. Condition of error displayed
If the temperature sensor detects
-50°C or lower for 5 seconds
continuously within 10 minutes
to 10 minutes 20 seconds after
compressor ON, the compressor
stops. When the compressor
is restarted automatically after
3-minute delay, if this anomaly
ocuurs 3 times within 40
minute.
4. Presumable cause
• Defective suction pipe
temperature sensor connection
• Defective suction pipe
temperature sensor
• Defective outdoor unit main
PCB
Note:
Error code
Remote control:
Content
1-time flash
Keeps flashing
5-time flash
Keeps flashing
Indoor display
RUN light
TIMER light
Green LED
Red LED
Outdoor unit
control PCB
Suction pipe temperature
sensor anomaly
Summary of Contents for FDC100VNA-W
Page 70: ... 19 PAC SM 309 69 LED2 Red LED1 Green ...
Page 72: ... 19 PAC SM 309 71 ...
Page 74: ... 19 PAC SM 309 73 LED2 Red LED1 Green ...
Page 76: ... 19 PAC SM 309 75 ...
Page 183: ... 19 PAC SM 309 182 1 e SRK series PHA012D402 ...
Page 184: ... 19 PAC SM 309 183 Screw ...
Page 185: ... 19 PAC SM 309 184 3 PHA012D402 ...
Page 186: ... 19 PAC SM 309 185 4 PHA012D402 ...