'19 • PAC-SM-309
-
96
-
WAIT
Communication error at
initial operation (2/3)
Keeps flashing
Keeps flashing
Stays OFF
2-time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
YES
Diagnosis for when the outdoor unit
main PCB LED is turned off
Shut down the breaker and back on
again the breaker 3 minutes later.
To check method for inverter PCB before
replacment of blown power source fuse.
YES
Does it reset normally?
NO
YES
Isn’t the outdoor
unit control power source fuse
(FDC100-140 VNA-W 30A) blown?
Note (1) 1-phase model only
※
FDC100-140 VSA-W
are except.
NO
YES
NO
Is AC220/240V or
AC380/415V detected at the noise filter
secondary side?
Isn’t fuse
〔
250V, 2A
〕
on the outdoor main
PCB blown?
NO
YES
Is DC15V detected
if the connector of outdoor fan motor
is disconnected?
NO
(1)
To next page
From previous page
Normal (Malfunction by
noise)
Replace noise filter.
Defective outdoor unit main
PCB
➞
Replace.
Defective outdoor fan
motor
Defective outdoor unit main
PCB
➞
Replace.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Faulty noise filter
• Faulty indoor unit control PCB
• Faulty outdoor unit main PCB
• Faulty fan motor
Note:
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
Summary of Contents for FDC100VNA-W
Page 70: ... 19 PAC SM 309 69 LED2 Red LED1 Green ...
Page 72: ... 19 PAC SM 309 71 ...
Page 74: ... 19 PAC SM 309 73 LED2 Red LED1 Green ...
Page 76: ... 19 PAC SM 309 75 ...
Page 183: ... 19 PAC SM 309 182 1 e SRK series PHA012D402 ...
Page 184: ... 19 PAC SM 309 183 Screw ...
Page 185: ... 19 PAC SM 309 184 3 PHA012D402 ...
Page 186: ... 19 PAC SM 309 185 4 PHA012D402 ...