'19 • PAC-SM-309
-
27
-
(22) Temporary stop input
In case of temporary stop, operation lamp of remote control lights, but indoor/outdoor unit stop the operation.
(a) In case of “level input” setting (Factory default)
Input signal to CnT-6 or CnTA is OFF → ON : Temporary stop
Input signal to CnT-6 or CnTA is OFF → ON : Normal operation
(b) In case of “pulse input” setting (Local setting)
It is effective only when the input signal is changed OFF→ON, and “temporary stop/normal operation” is inverted.
CnT-6 or CnTA input
OFF
ON
OFF
ON
ON
Actual operation
ON
ON
Temporary stop
Temporary stop
OFF
Remote control
ON
OFF
Normal operation/
Temporary stop zone
Normal
Temporary stop
Normal
Temporary stop
OFF
(23) Selection of cooling/heating external input function
(a) When “External input 1 setting: Cooling/heating” is set by the indoor unit function from remote control, the cooling or
heating is selected with CnT-6 or CnTA.
(b) When the external input 1 method selection: Level input is set by the indoor unit function:
・
CnT-6 or CnTA: OPEN → Cooling operation mode
・
CnT-6 or CnTA: CLOSE → Heating operation mode
(c) When the external input 1 method selection: Pulse input is set by the indoor unit function:
If the external input is changed OPEN → CLOSE, operation modes are inverted (Cooling → Heating or Heating →
Cooling).
(d) If the cooling/heating selection signal is given by the external input, the operation mode is transmitted to the remote
control.
■
Selection of cooling/heating external input function
External input selection
External input selection
Cooling/heating selection
External input method
⑤
Level
External terminal input
(CnT or CnTA)
Cooling/heating
Cooling/heating
(Competitive)
External terminal input
(CnT or CnTA)
Cooling/heating
Cooling/heating
(Competitive)
⑥
Pulse
Operation
OFF
Cooling zone
Heating zone
Cooling zone
Cooling zone
Heating zone
Heating zone
OFF
ON
OFF
OFF
ON
ON
ON
Cooling
Heating
Heating
Cooling
Cooling
Cooling
Auto
Auto
Cooling
Auto, cooling, dry mode command
↑
from remote control
↑
Heating, auto, heating mode command
from remote control
↑
Set “Cooling/
Heating” “Pulse”
↑
Auto, cooling, dry mode command
by remote control
↑
Auto, heating mode
command by remote control
↑
After setting “Cooling/heating selection”, the cooling/heating is
selected by the current operation mode.
During heating : Set at the heating zone (cooling prohibition zone).
During cooling, dry, auto and fan mode: Set
at cooling zone (heating prohibition zone).
Heating
Heating
Heating
Cooling
Heating
Cooling
Cooling
Note (1) Regarding the priority order for combinations of CnT and CnTA, refer to Page 23.
CnT-6 or CnTA input
OFF
ON
OFF
ON
Actual operation
ON
ON
Temporary stop
Temporary stop
OFF
Remote control
ON
OFF
Summary of Contents for FDC100VNA-W
Page 70: ... 19 PAC SM 309 69 LED2 Red LED1 Green ...
Page 72: ... 19 PAC SM 309 71 ...
Page 74: ... 19 PAC SM 309 73 LED2 Red LED1 Green ...
Page 76: ... 19 PAC SM 309 75 ...
Page 183: ... 19 PAC SM 309 182 1 e SRK series PHA012D402 ...
Page 184: ... 19 PAC SM 309 183 Screw ...
Page 185: ... 19 PAC SM 309 184 3 PHA012D402 ...
Page 186: ... 19 PAC SM 309 185 4 PHA012D402 ...