240
-
Bolt fastening positions
190
200
580
20
410
20
Air inlet
Air outlet
Anchor bolt position
(4 locations)
●
In installing the unit, fix the unit's legs with bolts specified below.
Use a long block to extend the width.
Fasten with bolts
(M10-12)
Use a thicker
block to anchor
deeper.
●
The protrusion of an anchor bolt on the front side must be kept within 15 mm.
●
Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.
●
Refer to the above illustrations for information regarding concrete foundations.
●
Install the unit in a level area. (With a gradient of 5 mm or less.)
Improper installation can result in a compressor failure, broken piping within the unit and abnormal noise generation.
Important
In case that the unit operates in cooling mode, when the outdoor temperature is –5°C or lower, please equip a flex flow adapter
and a snow guard hood (option) on the unit.
Refrigerant piping size selection
●
Please use pipes clean on both the inside and outside and free from contaminants harmful to operation such as sulfur,
oxides, dust, chips, oil, fat and water.
●
Use the following material for refrigerant piping.
Material: phosphorus deoxidized seamless copper pipe (C1120T-0, JIS H3300)
●
Thickness and size: Please select proper pipes according to the pipe size selection guideline.
(Since this unit uses R410A, Select pipes having a wall thickness larger than the specified minimum pipe thickness.
●
For branching pipes, use a genuine branching pipe set or header set at all times.
●
Install a branching pipe set, paying attention to the direction of attachment, after you have perused through the installation
manual supplied with it.
●
The length of piping from outdoor unit to first branch is 1.5m or more.
●
For the handling of service valves, please refer to 4-2. Piping work.
(4) Refrigerant piping
(i)
Determination of piping specifications
(Please select from the following matrix according to indoor unit specifications and installation site conditions)
Refrigerant piping restrictions
Please do not fail to observe the following pipe sizes and limitations of use.
A failure to observe this instruction can result in a compressor failure or performance degradation.
●
Please avoid forming any trap ( ) or bump ( ) in piping as they can cause fluid stagnation.
●
Maximum length (To the farthest indoor unit) .......................................... Within 70m
●
Equivalent length (To the farthest indoor unit) ......................................... Within 95m
●
Total pipe length (Combined total length of pipes) ................................ Within 100m
●
ø9.52 pipe length ....................................................................................... Within 50m
●
Height difference
(1) When the outdoor unit is above the indoor unit ................................. Within 30m
(2) When the outdoor unit is below the indoor unit ................................. Within 15m
(3) Height difference between indoor units in the same system .............. Within 15m
(4) Height difference between indoor units and first branch ................... Within 15m
Summary of Contents for FDC112KXEN6
Page 116: ... 112 4 Sensible heat capacity ...
Page 117: ... 113 ...
Page 118: ... 114 ...
Page 119: ... 115 ...
Page 120: ... 116 ...
Page 121: ... 117 ...
Page 122: ... 118 ...
Page 123: ... 119 ...
Page 124: ... 120 ...
Page 125: ... 121 ...
Page 126: ... 122 ...
Page 127: ... 123 ...
Page 128: ... 124 ...
Page 129: ... 125 ...
Page 130: ... 126 ...
Page 131: ... 127 ...
Page 132: ... 128 ...
Page 133: ... 129 ...
Page 134: ... 130 ...
Page 135: ... 131 ...
Page 136: ... 132 ...
Page 137: ... 133 ...
Page 138: ... 134 ...
Page 139: ... 135 ...
Page 140: ... 136 ...
Page 141: ... 137 ...
Page 142: ... 138 ...
Page 143: ... 139 ...
Page 144: ... 140 ...
Page 145: ... 141 ...
Page 146: ... 142 ...
Page 147: ... 143 ...
Page 148: ... 144 ...
Page 149: ... 145 ...
Page 150: ... 146 ...
Page 151: ... 147 ...
Page 152: ... 148 ...
Page 153: ... 149 ...
Page 154: ... 150 ...
Page 155: ... 151 ...
Page 156: ... 152 ...
Page 157: ... 153 ...
Page 158: ... 154 ...
Page 159: ... 155 ...
Page 160: ... 156 ...
Page 161: ... 157 ...
Page 162: ... 158 ...
Page 163: ... 159 ...
Page 164: ... 160 ...
Page 165: ... 161 ...
Page 166: ... 162 ...
Page 167: ... 163 ...
Page 168: ... 164 ...
Page 169: ... 165 ...
Page 170: ... 166 ...
Page 171: ... 167 ...
Page 172: ... 168 ...
Page 173: ... 169 ...