286
–
(c) Fan control during heating
During heating, fan speed is controlled in accordance with the low pressure (sensed by PSL).
(i) Initial fan speeds are as follows.
• Outdoor fan initial speed during heating
Model
Speed
All models
6th speed
(ii) During normal operation, the speed is changed in accordance with the low pressure value.
(4) Defrost (Defrost control)
• Temperature condition of defrosting
(a) Start conditions
(Standard specification or cold region specification can be selected by switching the jumper wire J15.)
Defrost operation will start, when outdoor unit whose compressor is operating under heating mode has satisfied all the
following conditions.
(i) When 33 minutes of cumulative compressor operation time has passed since heating operation started.
(ii) When 33 minutes of cumulative compressor operation time has passed since defrosting ended.
(iii) When 8 minutes has passed since the compressor turned ON from OFF status.
(iv) When 8minutes has passed since one outdoor fan turned ON from OFF status.
(v) After all above conditions have been met, when any of the following conditions is satisfied.
➀
When the outdoor heat exchanger temperature (sensed by Tho-R) and the ambient air temperature (sensed by
Tho-A) dropped below the defrosting start temperature in Fig. 1 for 30 seconds continuously
➁
When the suction pressure saturated temperature calculated by the low pressure (sensed by PSL) and the ambient
air temperature (sensed by Tho-A) dropped below the defrosting start temperature in Fig. 2 for 30 seconds
continuously
TR:
Heat e
xchanger temp
. (°C
)
TA: Ambient air temp. (°C)
TA: Ambient air temp. (°C)
Fig. 1
Cold region
Standard
(Factory setting)
Defrost start zone
-2
-6
-15
-19
-21
-25
-20
-15
6
Without J15
Cold region specification
With J15
SST
: Suction pressure saturated temp
. (°C)
Fig. 2
Cold region
Standard
(Factory setting)
Defrost start zone
-6
-10
-19
-23
-25
-29
-20
-15
6
Without J15
Cold region specification
With J15
(b) End conditions
Defrosting operation stops when any of the following conditions is satisfied.
(i) When 12 minutes has passed since defrost started
(ii) When the outdoor heat exchanger temperature (sensed by Tho-R) is detected 12°C or higher continuously for 10
seconds
(iii) When it has detected the high pressure (HP) ≥ 3.0MPa
Summary of Contents for FDC112KXEN6
Page 116: ... 112 4 Sensible heat capacity ...
Page 117: ... 113 ...
Page 118: ... 114 ...
Page 119: ... 115 ...
Page 120: ... 116 ...
Page 121: ... 117 ...
Page 122: ... 118 ...
Page 123: ... 119 ...
Page 124: ... 120 ...
Page 125: ... 121 ...
Page 126: ... 122 ...
Page 127: ... 123 ...
Page 128: ... 124 ...
Page 129: ... 125 ...
Page 130: ... 126 ...
Page 131: ... 127 ...
Page 132: ... 128 ...
Page 133: ... 129 ...
Page 134: ... 130 ...
Page 135: ... 131 ...
Page 136: ... 132 ...
Page 137: ... 133 ...
Page 138: ... 134 ...
Page 139: ... 135 ...
Page 140: ... 136 ...
Page 141: ... 137 ...
Page 142: ... 138 ...
Page 143: ... 139 ...
Page 144: ... 140 ...
Page 145: ... 141 ...
Page 146: ... 142 ...
Page 147: ... 143 ...
Page 148: ... 144 ...
Page 149: ... 145 ...
Page 150: ... 146 ...
Page 151: ... 147 ...
Page 152: ... 148 ...
Page 153: ... 149 ...
Page 154: ... 150 ...
Page 155: ... 151 ...
Page 156: ... 152 ...
Page 157: ... 153 ...
Page 158: ... 154 ...
Page 159: ... 155 ...
Page 160: ... 156 ...
Page 161: ... 157 ...
Page 162: ... 158 ...
Page 163: ... 159 ...
Page 164: ... 160 ...
Page 165: ... 161 ...
Page 166: ... 162 ...
Page 167: ... 163 ...
Page 168: ... 164 ...
Page 169: ... 165 ...
Page 170: ... 166 ...
Page 171: ... 167 ...
Page 172: ... 168 ...
Page 173: ... 169 ...