(5) Protective control
(a) Discharge pipe temperature control
If the discharge pipe temperature exceeds 105°C, compressor speed is reduced to suppress the rising of discharge pipe
temperature.
(i) If the discharge pipe temperature sensor detects 115°C or higher for 2 seconds continuously, it makes compressor
stopped. And if this anomaly occurs 5 times within 60 minute, it makes the unit anomalous stop (E36-1)
(ii) If the discharge overheat sensor (Td-DST) detects 5degC or lower for 10 minutes continuously, it makes compressor
stopped (liquid flooding anomaly).
And if this anomaly occurs 3 times within 60 minutes, it makes the unit anomalous stop (E36-3)
(b) High pressure control
(i) Compressor rotation speed protection control
➀
If high pressure sensor (PSH) detects 3.70MPa or higher, it makes compressor rotaion speed decreasing
➁
If high pressure sensor (PSH) still detects 3.70MPa or higher 5 seconds after
➀
control, it makes compressor
rotation speed decreasing more.
➂
If high pressure sensor (PSH) detects lower than 3.70MPa, this protective control is released.
(ii) High pressure protective control
If high pressure switch (63H1) is activated or if high pressure sensor (PSH) detects 4.14MPa or higher for 10
seconds continuously, it makes compressor stopped (High pressure anomaly).
And if this anomaly occurs 5 times within 60 minute, it makes the unit anomalous stop.(E40)
(c) Low pressure control
(i) Compressor rotation speed protection control
➀
If low pressure sensor (PSL) detects 0.18MPa or lower for 10 seconds continuously, it makes compressor
rotaion speed decreasing
➁
If low pressure sensor (PSL) still detects 0.18MPa or lower 30 seconds after
➀
control, it makes compressor
rotation speed decreasing more.
➂
If low pressure sensor (PSL) detects higher than 0.236MPa, this protective control is released.
(ii) Low pressure protective control
If high pressure sensor (PSL) detects 0.134MPa or lower for 30 seconds continuously, or if it detects 0.003MPa or
lower for 5 seconds continuously, it makes compressor stopped (Low pressure anomaly).
And if this anomaly occurs 5 times within 60 minute, it makes the unit anomalous stop.(E49)
(d) High pressure ratio protective control
➀
If pressure ratio is 8.0 or higher, it makes compressor rotaion speed decreasing
➁
If pressure ratio is 8.0 or higher 60 seconds after
➀
control, it makes compressor rotation speed decreasing more.
➂
If pressure ratio is 7.9 or lower, this protective control is released.
(e)
Over-current protection control (Current safe)
(i) Compressor capacity control
➀
Compressor speed is controlled by detecting the inverter’s T-phase current or secondary current.
➁
The control is changed at every ambient air temperature zone.
Ambient air temp. (ºC)
[Fig. 1]
Zone D
Zone C
Zone B
Zone A
34
36
38
40
43
45
Summary of Contents for FDC112KXEN6
Page 116: ... 112 4 Sensible heat capacity ...
Page 117: ... 113 ...
Page 118: ... 114 ...
Page 119: ... 115 ...
Page 120: ... 116 ...
Page 121: ... 117 ...
Page 122: ... 118 ...
Page 123: ... 119 ...
Page 124: ... 120 ...
Page 125: ... 121 ...
Page 126: ... 122 ...
Page 127: ... 123 ...
Page 128: ... 124 ...
Page 129: ... 125 ...
Page 130: ... 126 ...
Page 131: ... 127 ...
Page 132: ... 128 ...
Page 133: ... 129 ...
Page 134: ... 130 ...
Page 135: ... 131 ...
Page 136: ... 132 ...
Page 137: ... 133 ...
Page 138: ... 134 ...
Page 139: ... 135 ...
Page 140: ... 136 ...
Page 141: ... 137 ...
Page 142: ... 138 ...
Page 143: ... 139 ...
Page 144: ... 140 ...
Page 145: ... 141 ...
Page 146: ... 142 ...
Page 147: ... 143 ...
Page 148: ... 144 ...
Page 149: ... 145 ...
Page 150: ... 146 ...
Page 151: ... 147 ...
Page 152: ... 148 ...
Page 153: ... 149 ...
Page 154: ... 150 ...
Page 155: ... 151 ...
Page 156: ... 152 ...
Page 157: ... 153 ...
Page 158: ... 154 ...
Page 159: ... 155 ...
Page 160: ... 156 ...
Page 161: ... 157 ...
Page 162: ... 158 ...
Page 163: ... 159 ...
Page 164: ... 160 ...
Page 165: ... 161 ...
Page 166: ... 162 ...
Page 167: ... 163 ...
Page 168: ... 164 ...
Page 169: ... 165 ...
Page 170: ... 166 ...
Page 171: ... 167 ...
Page 172: ... 168 ...
Page 173: ... 169 ...