Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
347
–
E36
E36-3
Liqiud flooding anomaly
Keeps flashing Stays Off
Keeps flashing 3 times flash
1. Applicable model
5. Troubleshooting
KXE6 multi outdoor units
Diagnosis
Countermeasure
Is the unit
installation environment
within the range of
limitation?
Is the
refrigerant amount and
piping length
OK?
Is
insertion of
the thermistor connector into
the connector on outddoor
control PCB
OK?
Is
the temperature
thermistors of discharge pipe,
suction pipe, Tho-H and indoor
heat exchanger OK?
Is high pressure
thermistor OK?
Save data for 30 minutes before stopping in Mente PC
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
Is the
connected number
of indoor units checked by
Mente PC same as that
mentioned in utility
drawing?
After restarting,
does it recur?
Reset the power and restart
Is the
operation of
indoor EEV OK ?
(at cooling)
Is the operation of outdoor
EEVH OK? (at heating)
Is the operation of
outdoor EEVSC OK?
(at heating and
cooling)
YES
Check and save the data of
operating condition
Check ROM version
Check operation of SV1, SV2
Propose the client to
improve
Adjust refrigerant amount
properly (Check whether
the charged amount is
excess)
If the piping length is less
than 5m, calculate the
correct charging amount
and reduce excessive
refrigerant amount
Connect the signal wires
between indoor and
outdoor units securely.
Insert the connector
securely
Replace the thermistor
after checking whether the
thermistor characteristics is
OK ot not.
Restart operation and check
it, as much as possible,
under the operating
conditions for 30 minutes
before error occurred.
Wait and see
If possible, continue
to collect data (Keep
connecting Mente PC)
Replace EEV coil or EEV
main body.
Check refrigerant amount
again
2. Error detection method
When it detects that the overheat
temperature of discharge pipe
decreased
3. Condition of error displayed
If the overheat temperature
of discharge pipe is detected
5degC or lower for 10 minute
continuously.
If the compressor stop is
detected 3 times within 60
minutes
4. Presumable cause
• Faulty discharge pipe
temperature thermistor
• Faulty high pressure
thermistor
• Faulty connection signal wires
between indoor and outdoor
units
• Excessive refrigerant amount
• Faulty indoor EEV
• Faulty indoor heat exchanger
temperature thermistor
• Faulty outdoor EEVH
• Faulty suction pipe
temperature thermistor or
faulty low pressure thermistor
• Falty outdoor EEVSC
• Faulty Tho-H temperature
thermistor
• Piping length is out of
limitation range
Note:
Summary of Contents for FDC112KXEN6
Page 116: ... 112 4 Sensible heat capacity ...
Page 117: ... 113 ...
Page 118: ... 114 ...
Page 119: ... 115 ...
Page 120: ... 116 ...
Page 121: ... 117 ...
Page 122: ... 118 ...
Page 123: ... 119 ...
Page 124: ... 120 ...
Page 125: ... 121 ...
Page 126: ... 122 ...
Page 127: ... 123 ...
Page 128: ... 124 ...
Page 129: ... 125 ...
Page 130: ... 126 ...
Page 131: ... 127 ...
Page 132: ... 128 ...
Page 133: ... 129 ...
Page 134: ... 130 ...
Page 135: ... 131 ...
Page 136: ... 132 ...
Page 137: ... 133 ...
Page 138: ... 134 ...
Page 139: ... 135 ...
Page 140: ... 136 ...
Page 141: ... 137 ...
Page 142: ... 138 ...
Page 143: ... 139 ...
Page 144: ... 140 ...
Page 145: ... 141 ...
Page 146: ... 142 ...
Page 147: ... 143 ...
Page 148: ... 144 ...
Page 149: ... 145 ...
Page 150: ... 146 ...
Page 151: ... 147 ...
Page 152: ... 148 ...
Page 153: ... 149 ...
Page 154: ... 150 ...
Page 155: ... 151 ...
Page 156: ... 152 ...
Page 157: ... 153 ...
Page 158: ... 154 ...
Page 159: ... 155 ...
Page 160: ... 156 ...
Page 161: ... 157 ...
Page 162: ... 158 ...
Page 163: ... 159 ...
Page 164: ... 160 ...
Page 165: ... 161 ...
Page 166: ... 162 ...
Page 167: ... 163 ...
Page 168: ... 164 ...
Page 169: ... 165 ...
Page 170: ... 166 ...
Page 171: ... 167 ...
Page 172: ... 168 ...
Page 173: ... 169 ...