101
–
‘19 • KX-SM-318
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E39
E39-1
Discharge pipe temperature
sensor anomaly (Tho-D1)
Keeps flashing Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the
connector of
sensor connected
properly?
Are the
characteristics of
sensor OK? *3
*3
Check several times to prove any poor connection.
Temperature-resistance characteristics of discharge
pipe temperature sensor (Tho-D1)
Save data for 30 minutes before stopping in Mente PC
NO
NO
YES
Temperature (°C)
Temperature sensor
resistance (kΩ)
0
20
40
60
80
100
120
140
160
180
200
0
20 40
60
80 100 120 140 160
Check and save the data of
operating condition.
Check the conditions whether
it occurs immediately after the
power on or during operation
or stopping.
Check the sensed value.
Compare the temperature
on Mente PC with actual
measured value.
Insert the connector securely.
Replace sensor (Tho-D1).
Replace outdoor unit control
PCB.
2. Error detection method
Detection of anomalously low
temperature (resistance) of
Tho-D1
3. Condition of error displayed
• If 3°C or lower is detected for
5 seconds continuously within
10 minutes to 10 minutes
20 seconds after the compressor
ON, the compressor stops. And after
3 minutes delay, the compressor
starts again automatically, but if this
anomalous temperature is detected
3 times within 40 minutes after the
initial detection.
4. Presumable cause
• Broken sensor harness or
the internal wire of sensing
section (Check the molded
section as well)
• Disconnection of sensor
harness connection
(connector)
• Outdoor unit control PCB
anomaly
Note:
YES
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E40
E40
High pressure anomaly
(63H1-1 activated)
Keeps flashing Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
YES
NO
Save data for 30 minutes before stopping in Mente PC
Connect a pressure gauge and
restart operation.
Was 63H1
activated at 4.15MPa
or higher?
Does the sensed
value of the high pressure
sensor show 4.15MPa?
(Normal?)
Are the
63H1-1 OK?
Are the connector and/or
harnesse
OK?
Are the
service valves fully
open?
Is it
stop at 4.15MPa of gauge
pressre ?
Is there any
clogging in the refrigerant
circuit ?
NO
NO
YES
Check and save the data of
operating condition.
Check the sensed value of
high pressure sensor when the
63H1-1 is activated.
Check whether the high
pressure switch is activated
at the sensed value of high
pressure sensor.
High pressure sensor
anomaly is suspicious.
Check high pressure sensor
itself according to the
troubleshooting procedure of
E54, after retarting operation.
(If the high pressure sensor
[PSH] fails, replace it)
If the connector is
disconnected or the harness
is broken, correct it.
Also check whether the
high pressure switch is
properly mounted or not.
Open operation valve.
Check it, as much as
possible, under the
operating conditions for
30 minutes before error
occurred.
Replace outdoor control
PCB.
Remove clogs.
Check items (condenser
side):
• Filter clogging
• Air flow volume (Fan
motor)
• Short-circuit of air flow
2. Error detection method
When high pressure switch
63H1-1 is activated
3. Condition of error displayed
• If high pressure exceeds
4.15MPa
• If 63H1-1 is activated 5 times
within 60 minutes
• If 63H1-1 is activated for 60
minutes continuously
4. Presumable cause
• Short-circuit of airflow
at condenser side of heat
exchanger/Disturbance of
airflow/Clogging filter/Fan
motor anomaly
• Disconnection of high
pressure switch connector
• Breakage of high pressure
switch harness
• Closed service valves
• High pressure sensor anomaly
• High pressure switch anomaly
Note:
If the error does not recur, connect the Mente PC and continue to collect data.
YES
YES
YES
YES
NO
NO
NO