103
–
‘19 • KX-SM-318
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E41(E51)
E41(E51)-1
Power transistor overheat
Keeps flashing Stays Off
Keeps flashing 1 time
fl
ash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the
connection of power
transistor temperature sensor
OK?
(Check short-circuit or breakage
of harness)
Is the
characteristics of power transitor
temperature sensor OK? *
* Refer the characterristics
of power transistor temperature
sensor to E56
Is the fixing
of power transistor OK?
(Check tightening of screws or
application of radiation
silicon)
Save data for 30 minutes before stopping in Mente PC
Does the outdoor fan run ?
Does the
error recur when restarting?
Is the
cooling fan for inverter running?
Is 15V
of power for control PCB
detected?
Reset power source and restart
After power OFF
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
Check and save the data of
operating conditions.
Check the temperature of
power transistor.
Check the operation of
outdoor fan and cooling fan.
Repair it according to the
troubleshooting procedure
of E48.
Check it as much as
possible under the operating
conditions for 30 minutes
before error occurred.
Wait and see.
Continue to obain data, if
possible (Keep connecting
the Mente PC).
If the cooling fan does not
run in spite of the operation
ON range, check the
voltage at the connector of
cooling fan.
If the 220/240V is detected,
repalce cooling fan motor.
If 0V is detected, replace
outdoor unit control PCB.
After checking the loose
connection of connetor
or breakage of harness,
replace inverter PCB.
Connect the connector of
thermistor securely.
Or replace power transistor
temperature sensor.
Replace power transistor
temperature sensor.
Fix power transistor on to
the radiation
fi
n with proper
application of radiation
silicon.
Replace power transistor.
2. Error detection method
When anomalously high
temperature is detected by
power transistor temperature
sensor (Tho-P1)
3. Condition of error displayed
Anomalously high temperature
of power transistor is detected 5
times within 60 minutes (E41).
Or it is detected for 15 minutes
continuously
(E51)
4. Presumable cause
• Power transistor anomaly
• Power transistor temperature
sensor anomaly
• Improperly fixing of power
transistor to radiator fin
• Inverter PCB anomaly
• Outdoor fan motor anomaly
• Anomalous cooling fan motor
for inverter
• Inadequate installation space
of outdoor unit
Note:
The operating conditions of cooling fan for inverter is shown in the right figure
If the error does not recur, connect the Mente PC and continue to collect data.
81°C
Power transistor sensor temperature
OFF
ON
85°C
E42
E42
Current cut (1)
Stays Off
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the
power source
voltage OK?
Are the
service valves
opened?
Continue to next page
(1) FDC121-155KXZEN1:
FDC121-155KXZES1 :
1.172
Ω
or more at 20°C
0.293
Ω
or more at 20°C
NO
NO
Is the
high pressure during
operation
OK?
NO
Is the
checked result
of insulation resistance
and resistance between
terminals (1) of
compressor motor
OK?
NO
Check power source.
Open the valves.
Check refrigerant amount
and refregerant circuit.
*In case of transitional
increase of high pressure
and/or test run, several
times restarting may
recover it, because
liquid refrigerant in the
compresser is discharged
from the compressor.
Replace compressor.
2. Error detection method
In order to prevent from
overcurrent of inverter,
if the current exceeds the
compressor stopping.
3. Condition of error displayed
If the output current of inveter
makes the compressor stopping.
After 3-minute delay, the
compressor restarts, but if
this amonaly occurs 4 times
within 30 minutes after the intial
detection.
4. Presumable cause
• Open the valves
• Faulty power source
• Insufficient refrigerant amount
• Faulty compressor
• Faulty power transistor
module
Note:
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
YES
YES
YES
Summary of Contents for FDC121KXZEN1
Page 159: ... 158 19 KX SM 318 ...
Page 161: ... 160 19 KX SM 318 ...
Page 162: ... 161 19 KX SM 318 ...