E45
E45
Communication error between
inverter PCB and outdoor unit control PCB
Stays Off
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Are the
connectors of inverter
PCB and outdoor unit control
PCB OK?
Are
both JSW10, 11
on the inverter PCB
OFF?
Is the
connection
between inverter PCB
and outdoor unit control
PCB OK ?
Save data for 30 minutes before stopping in Mente PC.
NO
NO
Is LED on the inverter
PCB flashing?
NO
NO
Does it become normal?
Replace outdoor unit control PCB.
YES
NO
Check and save the data of
operating conditions.
Insert the connectors
securely.
Switch OFF all
No power on inverter PCB
→
Find the cause.
• Anomalous fan motor
(FDC121-155KXZEN1 only)
• Faulty power circuit of
control PCB
(FDC121-155KXZEN1 only)
Connect the signal wires
correctly.
Replace inverter PCB.
OK
2. Error detection method
3. Condition of error displayed
If the communication between
inverter PCB and outdoor unit
control PCB is not established.
4. Presumable cause
• Faulty inverter PCB
• Faulty connector between
inverter PCB and outdoor unit
control PCB
• Faulty outdoor unit control PCB
Note:
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
YES
YES
YES
YES