107
–
‘19 • KX-SM-318
E45
E45
Communication error between
inverter PCB and outdoor unit control PCB
Stays Off
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Are the
connectors of inverter
PCB and outdoor unit control
PCB OK?
Are
both JSW10, 11
on the inverter PCB
OFF?
Is the
connection
between inverter PCB
and outdoor unit control
PCB OK ?
Save data for 30 minutes before stopping in Mente PC.
NO
NO
Is LED on the inverter
PCB flashing?
NO
NO
Does it become normal?
Replace outdoor unit control PCB.
YES
NO
Check and save the data of
operating conditions.
Insert the connectors
securely.
Switch OFF all
No power on inverter PCB
→
Find the cause.
• Anomalous fan motor
(FDC121-155KXZEN1 only)
• Faulty power circuit of
control PCB
(FDC121-155KXZEN1 only)
Connect the signal wires
correctly.
Replace inverter PCB.
OK
2. Error detection method
3. Condition of error displayed
If the communication between
inverter PCB and outdoor unit
control PCB is not established.
4. Presumable cause
• Faulty inverter PCB
• Faulty connector between
inverter PCB and outdoor unit
control PCB
• Faulty outdoor unit control PCB
Note:
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
YES
YES
YES
YES
E46
E46
Mixed address setting methods
coexistent in same network
Stays Off
Stays Off
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is E46 displayed?
Save data for 30 minutes before stopping in Mente PC.
NO
Is it
manual address
setting?
Reset the power source and restart operation.
Turn ON the power source
of outdoor unit system one
by one and check the unit
that starts up with the auto
address setting.
NO
Check and save the data of
operating condition.
Check which addess setting
method (auto or manual
setting) is applied to the
outdoor unit system on
which the error exsists.
Test run
* No action is taken
because it is judged
that the power source
reset was not done after
changing address.
Set address manually.
Replace outdoor unit PCB.*
(Defective rotary switch)
* Before replacement,
the rotary switch for
address setting is not
damaged. (It was
experienced that No. 5
on rotary switch was not
recognized.)
the indoor SW5-2 (100 of
order for indoor address
setting) is OK or not.
2. Error detection method
If the auto address setting
and manual address setting
are mixed in one Superlink
network.
3. Condition of error displayed
In case that the units with old
and new Superlink systems are
mixed in one Superlink
network, if both auto address
setting and manual address
setting are exsited.
4. Presumable cause
• Mistake in the address setting
• Mistake in the signal wire
connection
Note:
Caution:
unless the power is reset after
changing addess.
<Reference>
Error display at mixed address setting
Auto
Manual
Auto address setting
E31
E46
Manual address setting
E46
Normal
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
YES