–
11
–
‘19 • KX-SM-318
(b) RC-E5
(i) Sleep timer
Set the duration of time from the present to the time to turn off the air-conditioner.
It can be selected from 10 steps in the range from “OFF 1 hour later” to “OFF 10 hours later”. After the sleep timer
setting, the remaining time is displayed with progress of time in the unit of hour.
(ii) OFF timer
Time to turn OFF the air-conditioner can be set in the unit of 10 minutes.
(iii) ON timer
Time to turn ON the air-conditioner can be set. Indoor temperature can be set simultaneously.
(iv) Weekly timer
Timer operation (ON timer, OFF timer) can be set up to 4 times a day for each weekday.
(v) Timer operations which can be set in combination
Timer
OFF timer
ON timer
Weekly timer
Timer
OFF timer
ON timer
Weekly timer
Notes
(1)
:
Allowed
: Not
Item
Item
(2) Since the ON timer, sleep timer
and OFF timer are set in parallel, when the times to turn ON and OFF the air-conditioner are duplicated,
the setting of the OFF timer has priority.
(vii)
Combination of patterns which can be set for the timer operations
Note (1)
:
Allowed
: Not
Sleep time
Sleep time
Set OFF timer by hour
Weekly timer
Set ON timer by hour Set OFF timer by clock Set ON timer by clock
Set OFF timer by hour
Set ON timer by hour
Set OFF timer by clock
Set ON timer by clock
Weekly timer
(4) Hot start (Cold draft prevention at heating)
(a) Operating conditions
When either one of following conditions is satisfied, the hot start control is performed.
(i) From stop to heating operation
(ii) From cooling to heating operation
(iii) From heating thermostat OFF to ON
(iv) After completing the defrost operation (only on units with thermostat ON)
(b) Contents of operation
(i) Indoor fan motor control at hot start
1) Within 7 minutes after starting heating operation, the fan mode is determined depending on the condition of
thermostat (fan control with heating thermostat OFF).
a) Thermostat OFF
i) Operates according to the fan control setting at heating thermostat OFF.
ii) Even if it changes from thermostat OFF to ON, the fan continues to operate with the fan control at thermostat
OFF till the heat exchanger temperature sensor (Thi-R1 or R2, whichever higher) detects 35°C or higher.
iii) When the heat exchanger temperature sensor (Thi-R1 or R2, whichever higher) detects 35°C or higher, the fan
operates with the set air flow volume.
Summary of Contents for FDC121KXZEN1
Page 159: ... 158 19 KX SM 318 ...
Page 161: ... 160 19 KX SM 318 ...
Page 162: ... 161 19 KX SM 318 ...