12
–
'19 • KX-SM-318
b) Thermostat ON
i) When the heat exchanger temperature sensor (Thi-R1 or R2, whichever higher) detects 25°C or lower, the fan is
turned OFF and does not operate.
ii) When the heat exchanger temperature sensor (Thi-R1 or R2, whichever higher) detects 25°C or higher, the fan
operates with the fan control at heating thermostat OFF.
iii) When the heat exchanger temperature sensor (Thi-R1 or R2, whichever higher) detects 35°C or higher, the fan
operates with the set air flow volume.
c) If the fan control at heating thermostat OFF is set at the “Set air flow volume” (from the remote control), the fan
operates with the set air flow volume regardless of the thermostat ON/OFF.
2) Once the fan motor is changed from OFF to ON during the thermostat ON, the indoor fan motor is not turned OFF
even if the heat exchanger temperature sensor detects lower than 25°C.
Note (1) When the defrost operation signal is received, it complies with the fan control during defrost operation.
3) Once the hot start is completed, it will not restart even if the temperature on the heat exchanger temperature sensor
drops.
(ii) During the hot start, the louver is kept at the horizontal position.
(iii) When the fan motor is turned OFF for 7 minutes continuously after defrost operation, the fan motor is turned ON re-
gardless of the temperatures detected with the indoor heat exchanger temperature sensor (Thi-R1, R2).
(c) Ending condition
(i) If one of following conditions is satisfied during the hot start control, this control is terminated, and the fan is operated
with the set air flow volume.
1) Heat exchanger temperature sensor (Thi-R1 or R2, whichever higher) detects 35°C or higher.
2) It has elapsed 7 minutes after starting the hot start control.
(5) Hot keep
Hot keep control is performed at the start of the defrost operation.
(a) Control
(i) When the indoor heat exchanger temperature (detected with Thi-R1 or R2) drops to 35°C or lower, set the indoor fan
to the low speed tap of each setting.
(ii) During the hot keep, the louver is kept at the horizontal position.
(b) Ending condition
When the indoor fan is at the lower tap at each setting, it returns to the set air flow volume as the indoor heat exchanger
temperature rises to 45°C or higher.
(6) Auto swing control
Note Even if [Auto Swing] is selected, the louver position with anti draft function is fixed to position 1.
(a) RC-EX3A
(i) Louver control
1) To operate the swing louver when the air-conditioner is operating, press the “Direction” button on the TOP screen of
remote control. The wind direction select screen will be displayed.
2) To swing the louver, touch the “Auto swing” button. The lover will move up and down. To fix the swing louver at a
position, touch one of [1] - [4] buttons. The swing lover will stop at the selected position.
3) Louver operation at the power on with a unit having the louver 4-position control function
The louver swings one time automatically (without operating the remote control) at the power on.
This allows the microcomputer recognizing and inputting the louver motor (LM) position.
(ii) Automatic louver level setting during heating
At the hot start and the heating thermostat OFF, regardless whether the auto swing switch is operated or not (auto
swing or louver stop), the louver takes the level position (in order to prevent blowing of cool wind). The louver
position display LCD continues to show the display which has been shown before entering this control.
(iii) Louver free stop control
If you touch the “Menu” → “Service setting” → “R/C function settings” buttons one after another on the TOP screen
of remote control, the “Upper / lower flap control” screen is displayed. If the free stop is selected on this screen, the
louver motor stops upon receipt of the stop signal from the remote control. If the auto swing signal is received from
the remote control, the auto swing will start from the position before the stop.