149
–
‘19 • KX-SM-318
8. To remove drain pump (DM)
(1) Remove the lid of control box.(See No.1)
(2) Remove the drain pan.(See No.4)
(3) Disconnect the drain pump connector(CNRx)
in the middle of wiring.
(4) Pull a hose to the arrow direc
tion
and remove it.
(5) Remove 2 drain pump assembly
fixin
g screws
and remove it.
9. To remove the temperature sensors (example"Thi-R1")
(1) Remove the lid of control box.(See No.1)
(2) Disconnect the Tho-R1 connector(CNNx) on PCB in control box.
(3) Remove the drain pan.(See No.4)
(4) Pull out the temperature sensor "Thi-R1" from the sensor holder.
10. To remove the heat exchanger assembly
(1) Remove the drain pan.(See No.3)
(2) Remove 3 pipe l
id fixing scr
ews and remove it.( mark)
(3) Remove 4 heat exchanger assy
fi
xing screws and remove it.( mark)
11. To remove the Electronic Expansion Valve (EEV)
(1) Remove the heat exchanger assembly.(See No.10)
(2) Remove the coil of EEV by pull out on the top.
(3) Remove welded part of EEV by welding.( mark)
PROCEDURE & PICTURES
Pipe lid
EEV
Coil of EEV
General view