151
–
‘19 • KX-SM-318
7. To remove drain pump (DM)
(1) Remove the lid of control box.(See No.1)
(2) Disconnect the drain pump connector(CNR)
on PCB in control box.
(3) Remove 4 drain pump assembly
fixing
screws and remove it.( mark)
(4) Pull a hose to the arrow direc
tion
and
remove it.
(5) Remove 3 drain pump
fixing scr
ews and
remove it.( mark)
8. To remove the temperature sensors (example"Thi-R1")
(1) Remove the lid of control box.(See No.1)
(2) Disconnect the Tho-R1 connector(CNNx) on PCB in control box.
(3) Remove the drain pan.(See No.3)
(4) Pull out the temperature sensor "Thi-R1" from the sensor holder.
9. To remove the heat exchanger assembly
(1) Remove the drain pan.(See No.3)
(2) Remove 4 pipe l
id fixing scr
ews
and remove it.( mark)
(3) Remove 4 heat exchan
g
er assy
fi
x
ing
screws and remove it.( mark)
10. To remove the electronic expansion Valve (EEV)
(1) Remove the heat excha
ng
er assembly.
(See No.7)
(2) Remove the coil of EEV by pull out
on the top.
(3) Remove welded part of EEV by weldin
g.
( mark)
PROCEDURE & PICTURES
Pipe lid
c
EEV
Coil of EEV
General view