153
–
‘19 • KX-SM-318
7. To remove the drain pump(DM) and
flot
switch(FS)
(1) Remove the lid of control box.(See No.1)
(2) Remove 5 drain pump assembly
fixin
g screws and remove it.
( mark)
(3) Disconnect the drain pump connector(CNR) on PCB in control box.
(4) Pull a hose to the arrow direc
tion
and remove it.
(5) Remove 3 drain pump
fixing scr
ews and remove it.( mark)
(6) Disconnect t
he flo
t switch connector(CNI) on PCB in control box.
(7) Remove t
he flo
t swit
ch fi
xing screw and remove it.( mark)
8. To remove the heat exchanger assembly
(1) Remove the bo
ttom p
anel(B).(See No.3)
(2) Remove 22 bo
ttom p
anel(F)
fixing scr
ews and remove it.( mark)
(3) Remove 2 drain pa
n fi
xing screws and remove it.( mark)
(4) Remove 4 heat exchanger assy
fi
xing screws and remove it.( mark)
9. To remove the Electronic Expansion Valve (EEV)
(1) Remove the heat exchanger assembly.(See No.8)
(2) Remove the coil of EEV by pull out on the top.
(3) Remove welded part of EEV by welding.( mark)
10. To remove the temperature sensors (example"Thi-R3")
(1) Remove the lid of control box.(See No.1)
(2) Disconnect the Thi-R3 connector(CNN) on PWB in control box.
(3) Remove the drain pan.(See No.8)
(4) Pull out the temperature sensor "Thi-R3" from the sensor holder.
PROCEDURE & PICTURES
Drain pan
Bo
tt
om panel(F)
EEV
Coil of EEV
General view