155
–
‘19 • KX-SM-318
6. To remove the control box
(1) Remove the lid of control box.(See No.1)
(2) Pull o
ff
all the inserted connectors.
(3) Remove 2 cotrol bo
x fi
xing screws and remove it.
7. To remove the heat exchanger assembly
(1) Remove the bo
ttom p
anel(B).(See No.3)
(2) Remove the drain
p
an.(See No.5)
(3) Remove the control box.(See No.6)
(4) Remove 4
p
i
pe
l
id fixing scr
ews and remove it.( mark)
(5) Remove 4 heat exchanger assy
fi
xing screws and
remove it.( mark)
8. To remove the drain pump(DM) and
flot
switch(FS)
(1) Remove the control box.(See No.6)
(2) Disconnect the drain
pump
connector(CNR)
on PCB in control box.
(3) Disconnect t
he flo
t switch connector(CNI)
on PCB in control box.
(4) Remove 4 dra
in p
um
p
assembly
fixin
g screws
and remove it.( mark)
(5) Pull a hose to the a
rrow direction
and remove it.
(6) Remove 3 dra
in p
um
p
fixing scr
ews and
remove it.( mark)
(7) Remove t
he flo
t swit
ch fi
xing screw and
remove it.( mark)
9. To remove the electronic expansion Valve (EEV)
(1) Remove the heat exchanger assembly.
(See No.7)
(2) Remove the coil of EEV by
pu
ll out
on the t
op.
(3) Remove welded
par
t of EEV by welding.
( mark)
10. To remove the temperature sensors (example"Thi-R1")
(1) Remove the lid of control box.(See No.1)
(2) Disconnect the Thi-R1 connector(CNN) on PCB in control box.
(3) Remove the drain
p
an.(See No.5)
(4) Pull out the
temperature sensor
"Thi-R3" from the sensor holder.
PROCEDURE & PICTURES
Pipe lid
EEV
Coil of EEV
General view