25
–
‘19 • KX-SM-318
(1) Operation of major functional components under each operation mode
Operation mode
Functional components
Cooling/Dehumidifying
Heating
Compressor
ON
Compressor
OFF
All stop by
remote control
Compressor
ON
Compressor
OFF
All stop by
remote control
Magnetic contactor for
compressor (52C1)
ON
ON
OFF
ON
ON
OFF
Crankcase heater (CH1)
ON/OFF*1
ON/OFF*1
ON
ON/OFF*1
ON/OFF*1
ON
Compressor (CM1)
Cooling low
pressure control
Stop
Stop
Heating high
pressure control
Stop
Stop
Fan motor (FMo1)
Normal control
Stop
Stop
Normal control
Stop
Stop
4-way valve (20S)
OFF
OFF
OFF
ON
ON
ON
OFF*2
Electronic expansion
valve for sub-cooling coil
(EEVSC)
Normal control Fully closed
Fully closed
Fully closed
Fully closed
Fully closed
Electronic expansion
valve for heating (EEVH) Fully open
Fully open
Fully open
Normal
control
Fully closed
Fully closed
Notes (1) Above list shows the conditions at steady state under each operation mode.
(2) *1 According to discharge superheat
(3) *2 It turns OFF after retaining ON condition for a certain minutes
(2) Compressor control
Compressor rotation speed at cooling (dehumidifying) and heating operations are as follows.
Unit: rps
Item
Model
Cooling (Dehumidifying) operation
Heating operation
FDC121KXZE1
40 - 77
20 - 110
FDC140KXZE1
40 - 100
20 - 110
FDC155KXZE1
40 - 106
20 - 110
(3) Outdoor fan control
(a) Control contents of fan tap and fan speed
Outdoor fan tap
Fan speed
Cooling
Heating
FMo1 [min
-1
]
FMo1 [min
-1
]
0th speed
0
0
1th speed
200
130
2th speed
300
300
3th speed
400
400
4th speed
500
500
5th speed
600
600
6th speed
740
740
7th speed
820
820
8th speed
870
870
(b) Fan control during cooling
During cooling and dehumidifying, fan speed is controlled in accordance with the high pressure (sensed by
PSH) and the ambient air temperature (sensed by Tho-A).
(i) Initial fan speeds are as follows.
Initial outdoor fan speed at cooling
Model
Ambient air temp. ≤ 5°C
5°C <
Ambient air temp. < 10°C 10°C ≤
Ambient air temp.
All models 1th speed
3th speed
5th speed
(ii) During normal operation, the speed is changed in accordance with the high pressure value.
(A) Normal control
1.4 Operation control function by the outdoor control