–
34
–
'19 • KX-SM-318
(5) Energy saving mode control
This control is effective, when [P04] of 7-segment display is set 000, 040, 060, 080 (except OFF)
(a) Control contents
(i) Compressor upper limit speed is changed according to the setting ratio.
(ii) Compressor upper limit speed is obtained by multiplying the rating speed (at cooling/heating) with the setting ratio
as follows.
OFF: Normal (Factory setting)
80%: 80% of rating compressor upper limit speed
60%: 60% of rating compressor upper limit speed
40%: 40% of rating compressor upper limit speed
0%: 0% of rating compressor upper limit speed (stop)
(Note) Compressor upper limit speed (rps) on energy saving mode is shown in following table
P04
Compressor upper limit speed (rps)
FDC121KXZEN/S1
FDC140KXZEN/S1
FDC155KXZEN/S1
Cooling
Heating
Cooling
Heating
Cooling
Heating
080
57
65
74
76
78
76
060
42
49
56
57
58
57
040
29
33
37
38
40
38
000
0
0
0
0
0
0
(iii) Except 0% of energy saving ratio, the following controls take precedence over this control.
• 4-way valve switching safeguard
• Defrost operation
• Oil return control
• Pump down operation control at removal of the unit
• Pump down control at start/stop
(6) Forced cooling/heating operation
(a) With this control, SW3-7 on the outdoor PCB is turned ON and CnS1 (equipped with short-circuit pin)
is shorted or opened so as to forcibly determined whether the indoor unit is operated for cooling or
heating. (It is valid at [P07]=2)
(b) If any operation mode other than the forcible mode is commanded from indoor unit, the mode unmatch
message is displayed on the remote control or others and operation enters in the FAN mode.
SW3-7
CnS1
Operation
ON
Open
Cooling only
Close
Heating only
(7) Emergency stop control
When one of indoor units receives the emergency stop signal from option device like as refrigerant leakage detector and the
information is transmitted to the outdoor unit, the outdoor unit stops operation and an emergency stop error is transmitted
to all indoor units running.
Make the emergency stop effective by remote control indoor function setting.
(a) When it receives the “Emergency stop” command from the indoor unit, it makes all stop by error.
(b) It shows the Error display “E63” and transmits the “Emergency stop” command to all indoor units.
(c) If the “Emergency stop reset” command is received from the indoor unit, the “Emergency stop reset”
command is transmitted to all indoor units.
Summary of Contents for FDC121KXZEN1
Page 159: ... 158 19 KX SM 318 ...
Page 161: ... 160 19 KX SM 318 ...
Page 162: ... 161 19 KX SM 318 ...