42
–
'19 • KX-SM-318
(ii) When the temperature is below -10.0°C for the display of discharge pressure saturated temperature and suction
pressure saturated temperature, the fraction after decimal point is rounded up. (Because the range of 7-segment
display is 3-digit.)
(iii) Precedence of display
①
[EXX] > [Related to check operation ([CHJ] > [CHU])] > [PdE] > [PdS]> [oPX] > [CXX]
②
If resetting from the display of
①
, it is switched to [C00].
③
If SW8 or SW9 is pressed during the display of
①
, it changes to [C00].
However, unless no button input is done for 10 seconds after change to [C00], it changes to the display of
①
automatically according to the precedence.
④
Display switching
Special display is the display other than [CXX].
When special
display occurs
Special display reset
or
button operation
Button operation
Button operation
No operation for 10 seconds*
* If the special display is reset in the meanwhile, it remains as [CXX].
[CXX]
[C00]
Special display