44
–
'19 • KX-SM-318
Code
No.
Contents of data display
Data display range Minimum
unit
Remarks
C30 Pressure switch
0,1
(0: Close, 1: Open)
–
Order of 100: 63H1-1
Order of 10: (Spare) 63H1-R
Order of 1: (Spare)
C31 External input
0,1
(0: Close, 1: Open)
–
Order of 100: CnS1
Order of 10: (Spare) CnS2
Order of 1: (Spare) CnG1
C32 External input
0,1
(0: Close, 1: Open)
–
Order of 100: (Spare) CnG2
Order of 10: (Spare)
Order of 1: (Spare)
C33 Relay output
0,1
(0: Close, 1: Open)
–
Order of 100: 52C-1
Order of 10: 20S
Order of 1: Crankcase heater 1
C34 Relay output
0,1
(0: Close, 1: Open)
–
Order of 100: (Spare) SV6
Order of 10: (Spare) SV7
Order of 1: (Spare) Cooling fan
C35 Relay output
0,1
(0: Close, 1: Open)
–
Order of 100: (Spare) SV1
Order of 10: (Spare) SV11
Order of 1: (Spare) SV12
C36 Relay output
0,1
(0: Close, 1: Open)
–
Order of 100: (Spare)
Order of 10: (Spare)
Order of 1: (Spare)
C37 External output
0,1
(0: Close, 1: Open)
–
Order of 100: External output (CnZ1)
Order of 10: (Spare) Operation output
Order of 1: (Spare) Anomalous output
C38 (Spare)
0,1
(0: Close, 1: Open)
–
Order of 100:
Order of 10:
Order of 1:
C39 (Spare)
0,1
(0: Close, 1: Open)
–
Order of 100:
Order of 10:
Order of 1:
<Outdoor unit information>
C40 Number of connected indoor units
0 - 50
1
C41 Capacity of connected indoor units
0 - 200
C42 Number of indoor units with thermostat ON
0 - 50
1
C43 Required Hz total
0 - 999
1Hz
C44 Cumulative compressor operation time
(CM1)
0 - 655
100h
C45 (Spare) Cumulative compressor operation time
(CM2)
0 - 655
100h
C46 Discharge pressure saturated temperature
-50 - 70
0.1°C
Range unable to display (-10°C or under) is in the unit of 1°C.
C47 Suction pressure saturated temperature
-50 - 30
0.1°C
Range unable to display (-10°C or under) is in the unit of 1°C.
C48 Sub-cooling coil temperature sensor 1
saturated pressure
-0.68 - 4.15
0.01
MPa
0 is omitted in negative range.
-0.68
[-.68]
C49 Cooling sub-cooling
0 - 50
0.1deg
C50 Heating overheat
0 - 50
0.1deg
C51 Sub-cooling coil overheat
0 - 50
0.1deg
C52 Discharge pipe overheat 1
0 - 50
0.1deg
C53 (Spare) Under-dome overheat 1
0 - 50
0.1deg
C54 Target cooling low pressure
0.00 - 2.00
0.01MPa
C55 Target heating high pressure
1.60 - 4.15
0.01MPa