48
–
'19 • KX-SM-318
Code
No.
Contents of data display
Data display range Minimum
unit
Remarks
<New Superlink setting>
P30
Superlink communication
satus
0,1
–
0: Current Superlink
1: New Superlink
P31 Start automatic address setting
0 : (Factory default)
0,1
–
0: Automatic address setting standby.
1: Automatic address setting start.
P32 Input starting indoor address
1 : (Factory default)
0 - 127
1
Specify the starting indoor address connected in one
refrigerant system for automatic address setting.
P33
Input the number of connected
indoor unis
1 : (Factory default)
1 - 24 (*)
1
Specify the number of indoor units connected in one
refrigerant system for automatic address setting.
(*) Maximum connectable number of indoor units for each
oudoor unit
P34 Polarity difinition
0 : (Factory default)
0,1
–
0: Network polarity not defined
1: Network polarity defined
P35
Indoor address clear
transmission 2
0 : (Factory default)
0,1
–
0: Does not transmit clear setting signal
1: Transmits clear setting signal (* Interlocked with [P34].)
For operation error protection
P36 (Spare)
–
P37 (Spare)
–
P38 (Spare)
P39 (Spare)
*1 Compressor stop cause
It shows the latest comprressor anomalous stop cause
Compressor stop cause
No.
At power on
0
Sensor disconnection
and/or short-circuit
Ambient air temperature
1
Outdoor heat exchanger temperture 1
2
Outdoor heat exchanger temperture 2
3
Discharge pipe temperature sensor (CM1)
4
Suction pipe temperature sensor
5
Sub-cooling temperature sensor (liquid side)
6
Sub-cooling temperature sensor (gas side)
7
Under-dome temperature sensor
8
Power transistor temperature sensor
9
Active filter temperature sensor
10
High pressure sensor
11
Low pressure sensor
12
Anomaly detection
HP anomaly
20
LP anomaly
21
Td1 anomaly
22
FMo1 anomaly
23
FMo2 anomaly
24
Inverter 1 current cut
25
Inverter 1 startup failure
26
Inverter 1 communication error
27
Inverter 1 anomalous compressor induced voltage and torque
28
Inverter 1 power tansistor overheat
29
Inverter 1 rotor lock
30
Liquid flooding anomaly
31
Stop by restriction
Outdoor operation mode heating/cooling switching
40
Heating overload protection
41