58
–
'19 • KX-SM-318
(2) Outdoor unit PCB setting
Code
Input
Remarks
SW1
Outdoor address No. (Order of 10)
SW2
Outdoor address No. (Order of 1)
SW3-1
Inspection LED reset
SW3-7
Forced heating/cooling
SW5-1
Test run switch
SW5-2
Test run Heating/Cooling
SW5-3
Pump down switch
SW7
Data erase/Write
SW8
7-segment display code No. increasing (order of 1)
SW9
7-segment display code No. increasing (order of 10)
SW4-1
Model selection
See following table.
SW4-2
SW4-3
SW4-4
SW4-7
Demand ratio selection
See following table.
SW4-8
Demand ratio selection
See following table.
J13
External input Level/Pulse
J15
Defrost start temperature Normal/Cold region
Notes (1) Jumper wires J13, J15 indicate short-circuit/open.
(2) Dip switch SW’s indicate OFF/ON.
Model selection with SW4-1 – SW4-4
Model
Switch
FDC121KXZEN1 FDC121KXZES1 FDC140KXZEN1 FDC140KXZES1 FDC155KXZEN1 FDC155KXZES1
SW4-1
0
0
1
1
0
0
SW4-2
0
0
0
0
1
1
SW4-3
1
1
1
1
1
1
SW4-4
1
0
1
0
1
0
Note (1) 0: OFF, 1: ON
Demand ratio selection with SW4-7, SW4-8
SW4-7
SW4-8
Compressor capacity (%)
0
0
80
1
0
60
0
1
40
1
1
0
Note (1) 0: OFF, 1: ON