66
–
'19 • KX-SM-318
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
None
Excessive noise/vibration (3/3)
–
–
–
–
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
[Adjustment
during commissioning]
Does noise/vibration occur when the
cooling/heating operation is
performed under anomalous
condition?
From 2/3
YES
If insufficient cooling
heating problem happens
due to anomalous operating
conditions at cooling
/heating, followings are
suspicious.
• Excessive charged
amount of refrigerant
• Insufficient charge
amount of refrigerant
• Intrusion of air, nitrogen,
etc.
In such case, it is necessary
to recover refrigerant,
vacuum-dry and recharge
refrigerant.
* Since there could be
many causes of noise/
vibration, the above may
not cover all.
In such case, check the
conditions when, where,
how the noise/vibration
occurs according to
following check points and
ask our consultation.
• Indoor/outdoor unit
• Cooling/heating/fan
mode
• Startup/stop/during
operation
• Operating condition
(Indoor/outdoor
temperatures and
pressures)
• Time it occurred
• Operation data retained
by remote control
or Mente PC such as
compressor rotation
speed, heat exchanger
temperature, EEV
opening degree and etc.
• Tone (If available, record
the noise)
• Any other anomalies
2. Error detection method
3. Condition of error displayed
4. Presumable cause
Note:
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
None
Excessive noise/vibration (2/3)
–
–
–
–
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
[Unit]
Does noise/vibration
occur when the cooling/
heating operation is
performing
normally?
Are the pipes
contacting with the
casing?
Is continuous
hissing or roaring sound
occurred?
From 1/3
To 3/3
Is hissing sounds
occurred at the startup or
stopping?
Is blowing
sound occurred at
the start/stop of defrost
operation during
heating mode?
Is cracking noise
occurred during heating
operation?
Is hissing
noise occurred
during cooling operation
or after operation
stopped?
YES
Rearrange the piping to
avoid contact with the
casing.
Noise/vibration is
generated when the
refrigerant gas or liquid
flows through inside of
piping of air-conditioner.
It is likely to occur
particularly during cooling
or defrost operation in the
heating mode. It is normal.
The noise/vibration occurs
when the refrigerant starts
or stops flowing. It is
normal.
When the defrost operation
starts or stops during heating
mode, the refrigerant
flow is reversed due to
switching 4-way valve.
This causes a large change
in pressure wich produces
a blowing sound. It may
also accompany the hissing
sound as mentioned above.
This is normal.
After the start or stop of
heating operation or during
defrost operation, abrupt
changes in temperature cause
resin parts to shrink or expand.
This is normal.
It is the sound produced
by the drain pump that
discharges drain from
indoor unit.
The pump continues to run
for 5 minutes after stopping
the cooling operation.
This is normal.
Apply the damper sealant
at the place considered
to be the sources such
as the pressure reducing
mechanism. (Expansion
valve, capillary tube, etc.)
2. Error detection method
3. Condition of error displayed
4. Presumable cause
Note:
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
NO