‘19 • KX-SM-318
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
None
Louver motor anomaly
Keeps flashing Stays Off
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
Is LM harness
broken?
Is there
any disconnection
or breakage of LM
connector?
Is LM locked?
Does LM turn
smoothly?
Is there
any problem on
the connection
link?
˜Check at the indoor unit side.
Is the
setting of air flow
direction change
prohibited?
Check how LS reacts
when the power is turned
OFF and ON again
Check the remote control whether
it is fixed free flow setting.
YES
Does the louver
link press LS till crick sound
can be heard?
NO
NO
YES
In cases of FDTW, FDTS and FDTQ
Does the
louver operate when
power on?
Notes (1) LM: Louver motor
(2) LS: Limit switch
YES
NO
NO
NO
NO
YES
Operate after waiting for more than 1 minute.
It is normal if LM can
be stopped by pressing
LS two times.
In cases of FDT, FDTC, FDE and FDK
Check the remote control whether
it is fixed free flow setting or not.
Correct it.
Repair harness.
Check connector (CnJ).
Replace louver motor.
Correct it.
Correct it.
Replace indoor unit control
PCB.
Correct it.
Adjust LM lever and then
check again.
• LS anomaly
Replace.
• Indoor unit control PCB
anomaly
Replace.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Louver motor anomaly
• Disconnection/breakage of
LM harness
• Limit switch anomaly
Note:
NO
NO
NO
YES
YES
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
None
Power source system anomaly
(Power source to indoor unit PCB)
Stays OFF Stays OFF
Stays OFF
1. Applicable model
5. Troubleshooting
FDT, FDTC, FDK series only
Diagnosis
Countermeasure
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
Is
AC 220-240V
detected between L-N on
the indoor terminal
block?
Note (2) LM: Louver motor
FM: Fan motor
Is AC
380/415V for 3-phase
unit detected between L1, L2, and L3 on
the outdoor terminal block
respectively?
Is DC8V detected
between CNP
①
-
②
?
Is JX1 open?
None of
actuator, etc. is
short-circuited?
Are fuses OK?
Is resistance
between
①
-
③
of CNW0
OK?
Is DC280V detected
between CNM FDT, FDTC:
①
-
④,
FDK:
①
-
③
?
Is resistance
to FM, LM and etc.
OK?
Note (1)
Check the fuse at the power source side.
(1)
(2)
anomaly
Replace it.
Wrong wiring or broken
wires between outdoor and
indoor units
Indoor unit PCB
anomaly
Replace it.
Replace FM, LM and etc.
Replace fuse.
Indoor unit PCB
anomaly
Replace it.
Replace related parts.
Defective indoor unit
PCB
Replace.
Open JX1.
Defective indoor unit
PCB → Replace.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Wrong connection or breakage
of connecting wires
• Blown fuse
• Indoor unit PCB anomaly
• Broken harness
Note: