71
–
‘19 • KX-SM-318
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
None
Power source system anomaly
(Power source to indoor unit PCB)
Stays OFF Stays OFF
Stays OFF
1. Applicable model
5. Troubleshooting
Except FDT, FDTC, FDK series
Diagnosis
Countermeasure
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
YES
YES
Is
AC 220-240V
detected between L-N on
the outdoor terminal
block?
Note (2)
Disconnect CNW1 on
models equipped with
transformer.
Note (3) LM: Louver motor
FM: Fan motor
Note (4)
⑤
for GND
Is AC
380/415V for 3-phase
unit detected between L1, L2, and L3 on
the outdoor terminal block
respectively?
Are fuses OK?
Is power
source between
①
-
③
of
CNW0 OK?
Is
DC5V detected
between
④
-
⑤
of
CNW2?
Is power
source to FM, LM and etc.
OK?
Note (1)
Check the fuse at the power source side.
(1)
(2)
(3)
(4)
Model equipped with
transformer (Tri)
Models other than
shown at left
Is DC18V or higher
detected between Red-
Red (CNW2) at the
transformer secondary
side?
anomaly
Replace it.
Wrong wiring or broken
wires between outdoor and
indoor units
Indoor unit control PCB or
power PCB
anomaly
Replace it.
Replace FM, LM and etc.
Replace fuse.
Indoor unit power PCB
anomaly
Replace it.
Indoor unit control PCB
anomaly
Replace it.
Replace transformer.
Indoor unit control PCB
anomaly
Replace it.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Wrong connection or breakage
of connecting wires
• Blown fuse
• Transformer anomaly
• Indoor unit power PCB
anomaly
• Broken harness
• Indoor unit control PCB
anomaly
Note:
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
None
Power source system error
(Power source to remote control)
Stays OFF
1. Applicable model
5. Troubleshooting
FDT, FDTC, FDK series only
Diagnosis
Countermeasure
Is the connection of the
remote control's wiring OK?
X (white), Y (black)
Does resetting the
power source return
it to normal?
NO
Does the re-measured
voltage between X and Y
in the indoor terminal block
exceed 15 VDC?
YES
NO
YES
NO
NO
YES
Does the voltage
between X and Y in the
indoor terminal block
exceed 15 VDC?
Remove wire for
the remote control
Power source reset
YES
Correct.
Remote control wire
breakage?
Replace remote control.
Malfunction by temporary
noise
Defective indoor unit
control PCB
Replace.
Remote control wire
breakage?
Replace remote control.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Remote control wire
breakage/short-circuit
• Defective remote control
• Malfunction by noise
• Broken harness
• Faulty indoor unit control
PCB
Note: