75
–
‘19 • KX-SM-318
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
WAIT
WAIT
(3)
Keeps flashing Stays Off
Keeps flashing Keeps flashing
1. Applicable model
5. Troubleshooting
All models
(No display on the remote
control after power ON)
Diagnosis
Countermeasure
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
No display on the remote
control after power ON
Does
indoor green LED keep
flashing?
Does
outdoor red LED flash
2-time?
Is
the connecting wires
between indoor and outdoor
units comnnected
properly?
Is
AC380-415V detected
between L1-L2, L2-L3, L3-L1
respectively at outdoor unit
terminal block?
Is
AC220-240V detected
between L-N at indoor unit
teminal block?
Is
The fuse on indoor unit control
PCB OK?
Is
AC18V or higher is
detected between Red-Red
at secondary side of indoor unit
transformer? (1)
Is
DC10-11V between
X-Y at indoor unit control PCB
side when removing
remote control ?
Note (1) except FDT
and FDTC
Fuse blown
Replace fuse.
Transformer anomaly.
Remote control wire
short-circuited.
Remote control anomaly.
Indoor unit control PCB
anomaly.
Remote control anomaly.
Breakage of connecting
wires of remote control
Correct the connecting
wires properly.
Outdoor unit control PCB
anomaly
Replace it.
Breakage of connecting
wire.
Noise
Indoor unit control PCB
anomaly
Replace it.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Fuse blown
• Noise filter anomaly
• Anomalous connection of
wire between PCBs
• Indoor unit control PCB anomaly
• Remote control anomaly
• Breakage of connecting wires
of remote control
• Outdoor unit control PCB anomaly
Note:
YES
YES
YES
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
WAIT
WAIT
(2)
Keeps flashing Stays Off
Keeps flashing Keeps flashing
1. Applicable model
5. Troubleshooting
All models
(In case of fuse blown, how
to check the unit before
replacement of fuse)
Diagnosis
Countermeasure
YES
YES
NO
NO
YES
NO
Isn't
there any short circuit
between phases of noise
filter?
Isn't
there any crack or damage
on power transistor
module or diode stack?
Isn't
there any anomaly on
reactor?
Replace noise filter
Replace reactor
Replace inverter PCB
Replace fuse.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Fuse blown
• Noise filter anomaly
• Anomalous connection of
wire between PCBs
• Indoor unit control PCB anomaly
• Remote control anomaly
• Breakage of connecting wires
of remote control
• Outdoor unit control PCB anomaly
Note: