Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E6
-
Indoor unit heat exchanger
temperature sensor anomaly (Thi-R)
Keeps flashing 1 time flash
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is
the connector of
sensor connected
properly ?
Regarding the characteristics of
the sensor, see the following chart
Are
the characteristics
of sensor OK?
*1
NO
NO
YES
*1
Check several times to prove any poor connection.
YES
T
empearture sensor resistance (kΩ
)
Temperature-resistance characreristics of indoor unit heat
exchanger temperature sensor (Thi-R1, R2, R3)
5kΩ at 25ºC
T
emperature (ºC)
Insert the connector
securely.
Replace sensor (Thi-R).
Replace indoor unit control
PCB.
2. Error detection method
Detection of anomalously low
temperature (resistance)
of Thi-R1, R2, R3
3. Condition of error displayed
•
If -50ºC or lower is
detected for 5 seconds
continuously, compressor
stops. After 3 minutes delay,
the compressor is restarted
automatically, but if this
anomaly occurs again within
60 minutes after the initial
detection.
•
Or if 70ºC or higher is
detected for 5 seconds
continuously.
4. Presumable cause
• Anomalous connecion
of indoor unit heat exchanger
temperature sensor
• Indoor unit heat exchanger
temperature sensor
anomaly
• Indoor unit control PCB anomaly
Note: