‘19 • KX-SM-318
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E16
-
Indoor fan motor anomaly
(FDT, FDTC series)
Keeps flashing 1 time flash
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
FDT, FDTC series only
Diagnosis
Countermeasure
NO
YES
YES
Does any
foreign matter intervene
in rotational area of fan?
Is DC280V
detected between
①
-
④
of
fan motor connector
CnM?
Does it become normal?
Is the fuse F2 blown?
Does the fan
rotate smoothly when turned
by hand?
YES
NO
NO
NO
YES
NO
YES
Reset the power source and restart.
(1)
Note (1)
④
is GND
Remove foreign matter.
Replace the fan motor.
Check power source
voltage.
Replace fan motor and
power PCB.
Replace fan motor. (If
the anomaly persists after
replacing the fan motor,
replace the indoor unit control
PCB.)
Malfunction by temporary
noise
2. Error detection method
Detected by revolution speed of
indoor fan motor
3. Condition of error displayed
When actual revolution speed of
indoor fan motor drops to lower
than 200min
-1
for 30 seconds
continuously, the compressor
and the indoor fan motor stop.
After 2 seconds delay, fan
motor starts again automatically,
but if this anomaly occurs 4
times within 60 minutes after
the initial detection.
4. Presumable cause
• Indoor fan motor anomaly
• Foreign matter at rotational
area of fan propeller
• Fan motor anomaly
• Dust on control PCB
• Blown fuse
• External noise, surge
Note:
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E12
-
Address setting error
by mixed setting method
Keeps flashing Keeps flashing
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Isn't the
automatic setting and
manual setting mixed in the address
setting method for indoor
units?
YES
NO
Review address setting.
Replace indoor unit control
PCB.
2. Error detection method
Automatic address setting and
manual adress setting are mixed
when setting adress of indoor
units
3. Condition of error displayed
Same as above
4. Presumable cause
Mistake in address setting for
indoor unit
Note:
Address setting method list (Figures in [ ] are for Previous Superlink models)
Models for new Superlink protocol
Models for Previous Superlink protocol
Indoor unit address setting Outdoor unit
address setting Indoor unit address setting
Outdoor unit
address setting
Indoor unit No. switch Outdoor unit No. switch Outdoor unit No. switch Indoor unit No. switch Outdoor unit No. switch Outdoor unit No. switch
Manual address setting
(New SL)
000-127
00-31
00-31
00-47
00-47
00-47
(Previous SL)
[00-47]
[00-47]
[00-47]
Automatic address setting
for single refrgerant system
(New SL)
000
49
49
49
49
49
(Previous SL)
Automatic address setting
for multiple refrgerant systems
(New SL)
000
49
00-31
Not available
(Previous SL)
Not available