91
–
‘19 • KX-SM-318
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E19
-
Indoor unit operation check,
drain pump motor check mode anomaly
Keeps flashing 1 time flash
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Indoor unit control PCB
anomaly
(Anomalous SW7)
Replace.
Turn SW7-1 on the indoor
unit control PCB OFF and
reset the power.
2. Error detection method
E19 occurs
3. Condition of error displayed
Same as above
4. Presumable cause
Mistake in SW7-1 setting
Due to forgetting to turn OFF
SW7-1 after indoor unit operation
check)
Note:
Indoor unit operation check/drain pump check mode
If the power is ON after SW7-1ON. indoor unit operation check/drain pump check mode can be established.
1) When the communication between remote control and indoor unit PCB is established 15 seconds after power ON,
it goes to indoor unit operation check.
2) When the communication between remote control and indoor unit PCB is not established, it goes to drain pump check
(CnB connector should be open before power ON)
Is SW7-1
on the indoor unit control
PCB ON?
E19 occurs when the
power ON
NO
YES
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E16
-
Indoor fan motor anomaly
(FDK series)
Keeps flashing 1 time flash
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
FDK series only
Diagnosis
Countermeasure
NO
YES
YES
Does any
foreign matter intervene
in rotational area of fan
impeller?
Is DC280V
detected between
①
-
③
of fan motor
connector CnM?
Does is become normal?
Does the fan
rotate smoothly when
turned by hand?
YES
NO
NO
NO
YES
(1)
Note (1)
③
for GND
Reset the power source and restart.
Remove foreign matter.
Replace fan motor.
Replace fan motor and
power PCB.
Replace fan motor. (If
this anomaly persists after
replacing the fan motor,
replace indoor unit control
PCB.)
Malfunction by temporary
noise
2. Error detection method
Detected by revolution speed of
indoor fan motor
3. Condition of error displayed
When actual revolution speed of
indoor fan motor drops to lower
than 200min
-1
for 30 seconds
continuously, the compressor
and the indoor fan motor stop.
After 3 seconds delay, fan motor
starts again automatically, but
if this anomaly occurs 4 times
within 60 minutes after the
initial detection.
4. Presumable cause
• Indoor fan motor anomaly
• Foreign matter at rotational
area of fan impeller
• Fan motor anomaly
• Dust on control PCB
• Blown fuse
• External noise, surge
Note: