97
–
‘19 • KX-SM-318
E36
E36-1
Discharge pipe temperature
error (Tho-D1)
Stays Off
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the unit
installation environment
within the range of
limitation?
Are the
refrigerant amount and
piping length
OK?
Is the
discharge pipe
temperature sensor
normal?
Save data for 30 minutes before stopping in Mente PC.
NO
NO
Is the
sensor connector
inserted to the PCB connector
properly?
NO
NO
Does it
recur after restarting
operation?
Reset the power and restart operation.
NO
YES
Check and save the data of
operating condition.
Check the ROM version.
Propose an improvement to
the customer.
Adjust the refrigerant
amount poperly.
(Check whether the
refrigerant amount is
(Check the gas leakage.)
Insert connectors securely.
Check if characteristics
are correct, referring to
the characteristics list
of E39 (Page 100) . And
if necessary, replace the
discharge pipe temperature
sensor.
Check it, as much as
possible, under the
operating conditions for
30 minutes before error
occurred.
Wait and see.
Continue to obtain data, if
possible.
(Keep connecting the
Mente PC.)
Check refrigerant amount
again.
2. Error detection method
Detection of anomalously high
temperature by the discharge
pipe temperature sensor
3. Condition of error displayed
When the discharge pipe
temperature sensor detects
115°C or higher the compressor
stops. After 3-minute delay,
the compressor starts again
automatically, but if this
anomaly occurs 5 times within
60 minutes after the initial
detection.
4. Presumable cause
• Defective discharge pipe
temperature sensor
• Defective outdoor unit control
PCB
• Insufficient amount of
refrigerant
• Insufficient air flow volume
• Short-circuit
Note:
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
YES
YES
YES
YES
E36
E36-3
Stays Off
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the unit
installation environment
within the range of
limitation?
Is the
refrigerant amount and
piping length
OK?
Is
insertion of
the sensor connector into
the connector on outdoor unit
control PCB
OK?
Is
the temperature
sensors of discharge pipe,
suction pipe, Tho-H and indoor
heat exchanger OK?
Is high pressure
sensor OK?
Save data for 30 minutes before stopping in Mente PC.
Is the
connected number
of indoor units checked by
Mente PC same as that
mentioned in utility
drawing?
After restarting,
does it recur?
Reset the power source and restart.
Is the
operation of
indoor EEV OK ?
(at cooling)
Is the operation of outdoor
EEVH OK? (at heating)
Is the operation of
outdoor EEVSC OK?
(at heating and
cooling)
Check and save the data of
operating condition.
Check ROM version.
Propose the client to
improve.
Adjust refrigerant amount
properly. (Check whether
the charged amount is
excess.)
If the piping length is less
than 5m, calculate the
correct charging amount
and reduce excessive
refrigerant amount.
Connect the signal wires
between indoor and
outdoor units securely.
Insert the connector
securely.
Replace the sensor
after checking whether the
sensor characteristics is
OK ot not.
Restart operation and check
it, as much as possible,
under the operating
conditions for 30 minutes
before error occurred.
Wait and see.
If possible, continue
to collect data. (Keep
connecting Mente PC.)
Replace EEV coil or EEV
main body.
Check refrigerant amount
again.
2. Error detection method
When it detects that the overheat
temperature of discharge pipe
decreased
3. Condition of error displayed
If the overheat temperature
of discharge pipe is detected
5ºC or lower for 10 minute
continuously.
If the compressor stop is
detected 3 times within 60
minutes
4. Presumable cause
• Faulty discharge pipe
temperature sensor
• Faulty high pressure sensor
• Faulty connection signal wires
between indoor and outdoor
units
• Excessive refrigerant amount
• Faulty indoor EEV
• Faulty indoor heat exchanger
temperature sensor
• Faulty outdoor EEVH
• Faulty suction pipe
temperature sensor or
faulty low pressure sensor
• Falty outdoor EEVSC
• Faulty Tho-H temperature
sensor
• Piping length is out of
limitation range
Note:
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
NO
YES
YES