98
–
'19 • KX-SM-318
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
*1 E37-1: one time flash (Tho-R1), E37-5: 5 time flash (Tho-SC), E37-6: 6 time flash (Tho-H)
E37
E37-1, 5, 6*1
Outdoor unit heat exchanger
temperature sensor (Tho-R) and subcooling coil
temperature sensor (Tho-SC,-H) anomaly
Keeps flashing Stays Off
Keeps flashing
*1
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the
connector of
sensor connected
properly?
Are the
characteristics of
sensor OK?*2
*2
Check several times to prove any poor connection.
Outdoor heat exchanger temperature sensor (Tho-R1)
Sub-cooling coil sensor (Tho-SC, Tho-H)
Temperature-resistance characteristics
Save data for 30 minutes before stopping in Mente PC
NO
NO
YES
Temperature (°C)
5kΩ at 25°C
T
emperature sensor resistance (kΩ
)
Check and save the data of
operating conditions.
Check the conditions whether
it occurs immediately after the
power on or during operation
or stopping.
Check the sensed value.
Compare the temperature
on Mente PC with actual
measured value.
Insert the connector
securely.
Replace sensor .
(Tho-SC, Tho-H, Tho-R)
Replace outdoor unit control
PCB.
2. Error detection method
Detection of anomalously low
temperature (resistance)
of Tho-R or Tho-SC or Tho-H
3. Condition of error displayed
• If -50°C or lower is detected for 5
seconds continuously within 2 minutes to
2 minutes 20 seconds after the compressor
ON, the compressor stops. And after
3 minutes delay, the compressor starts
again automatically, but if this anomalous
temperature is detected 3 times within 40
minutes after the initial detection.
• If -50°C or lower is detected for 5 seconds
continuously within 20 seconds after power ON
4. Presumable cause
• Broken sensor harness or
the internal wire of sensing
section (Check the molded
section as well)
• Disconnection of sensor
harness connection
(connector)
• Outdoor unit control PCB
anomaly
Note:
YES
Summary of Contents for FDC121KXZEN1
Page 159: ... 158 19 KX SM 318 ...
Page 161: ... 160 19 KX SM 318 ...
Page 162: ... 161 19 KX SM 318 ...