103
–
'18 • KX-SM-292
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E40
E40
High pressure anomaly
(63H1-1activated)
Keeps flashing Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
YES
NO
Save data for 30 minutes before stopping in Mente PC
Connect a pressure gauge and
restart operation.
Was 63H1
activated at 4.15MPa
or higher?
Does the sensed
value of the high pressure
sensor show 4.15MPa?
(Normal?)
Are the
63H1-1 OK?
Are the connector and/or
harnesse
OK?
Are the
service valves fully
open?
Is it
stop at 4.15MPa of gauge
pressre ?
Is there any
clogging in the refrigerant
circuit ?
NO
NO
YES
Check and save the data of
operating condition.
Check the sensed value of
high pressure sensor when the
63H1-1 is activated.
Check whether the high
pressure switch is activated
at the sensed value of high
pressure sensor.
High pressure sensor
anomaly is suspicious.
Check high pressure sensor
itself according to the
troubleshooting procedure of
E54, after retarting operation.
(If the high pressure sensor
[PSH] fails, replace it)
If the connector is
disconnected or the harness
is broken, correct it.
Also check whether the
high pressure switch is
properly mounted or not.
Open operation valve.
Check it, as much as
possible, under the
operating conditions for
30 minutes before error
occurred.
Replace outdoor control
PCB.
Remove clogs.
Check items (condenser
side):
• Filter clogging
• Air flow volume (Fan
motor)
• Short-circuit of air flow
2. Error detection method
When high pressure switch
63H1-1 is activated
3. Condition of error displayed
• If high pressure exceeds
4.15MPa
• If 63H1-1 is activated 5 times
within 60 minutes
• If 63H1-1 is activated for 60
minutes continuously
4. Presumable cause
• Short-circuit of airflow
at condenser side of heat
exchanger/Disturbance of
airflow/Clogging filter/Fan
motor anomaly
• Disconnection of high
pressure switch connector
• Breakage of high pressure
switch harness
• Closed service valves
• High pressure sensor anomaly
• High pressure switch anomaly
Note:
If the error does not recur, connect the Mente PC and continue to collect data.
YES
YES
YES
YES
NO
NO
NO
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E41(E51)
E41(E51)-1
Power transistor overheat
Keeps flashing Stays Off
Keeps flashing 1 time
fl
ash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the
connection of power
transistor temperature sensor
OK?
(Check short-circuit or breakage
of harness)
Is the
characteristics of power transitor
temperature sensor OK? *
* Refer the characterristics
of power transistor temperature
sensor to E56
Is the fixing
of power transistor OK?
(Check tightening of screws or
application of radiation
silicon)
Save data for 30 minutes before stopping in Mente PC
Does the outdoor fan run ?
Does the
error recur when restarting?
Is the
cooling fan for inverter running?
Is 15V
of power for control PCB
detected?
Reset power source and restart
After power OFF
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
Check and save the data of
operating conditions.
Check the temperature of
power transistor.
Check the operation of
outdoor fan and cooling fan.
Repair it according to the
troubleshooting procedure
of E48.
Check it as much as
possible under the operating
conditions for 30 minutes
before error occurred.
Wait and see.
Continue to obain data, if
possible (Keep connecting
the Mente PC).
If the cooling fan does not
run in spite of the operation
ON range, check the
voltage at the connector of
cooling fan.
If the 220/240V is detected,
repalce cooling fan motor.
If 0V is detected, replace
outdoor unit control PCB.
After checking the loose
connection of connetor
or breakage of harness,
replace inverter PCB.
Connect the connector of
thermistor securely.
Or replace power transistor
temperature sensor.
Replace power transistor
temperature sensor.
Fix power transistor on to
the radiation
fi
n with proper
application of radiation
silicon.
Replace power transistor.
2. Error detection method
When anomalously high
temperature is detected by
power transistor temperature
sensor (Tho-P1)
3. Condition of error displayed
Anomalously high temperature
of power transistor is detected 5
times within 60 minutes (E41).
Or it is detected for 15 minutes
continuously
(E51)
4. Presumable cause
• Power transistor anomaly
• Power transistor temperature
sensor anomaly
• Improperly fixing of power
transistor to radiator fin
• Inverter PCB anomaly
• Outdoor fan motor anomaly
• Anomalous cooling fan motor
for inverter
• Inadequate installation space
of outdoor unit
Note:
The operating conditions of cooling fan for inverter is shown in the right figure
If the error does not recur, connect the Mente PC and continue to collect data.
81°C
Power transistor sensor temperature
OFF
ON
85°C
Summary of Contents for FDC224KXZME1