104
–
'18 • KX-SM-292
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E42
E42-1
Current cut (CM1)
Keeps flashing Stays Off
Keeps flashing 1 time
fl
ash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the
coil resistance and insulation
(megger check) of compressor
motor OK?
Is 15V
of power for control PCB
detected? Is the outdoor fan motor
OK? (Refer the checking method of
15V
in page63)
Do you
have inverter checker for
judging whether inverter PCB is
OK or not?
After power OFF,
Remove the 1-3 layers
of control box
Is the
checked result by measuring
the resistance beween each terminal
of power transistor module OK?
(Are there any short-
circuit?)
Is the
checked result by
inverter checker
OK?
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
Save data for 30 minutes before stopping in Mente PC
Does the outdoor fan run ?
Reset power source and restart
Does E42 recur?
Check and save the data of
operating conditions.
Check pressure anomaly.
Check the operation of
outdoor fan.
Replace compressor.
Check the capillary tube
and stariner of oil separator.
If necessary, replace the
capillary tube and strainer
as well.
Repair it according to the
troubleshooting of E48.
Replace inverter PCB or
outdoor fan motor.
Check it as much as
possible under the
operating conditions for
30 minutes before error
occurred.
Wait and see.
Continue to obain data, if
possible (Keep connecting
the Mente PC).
Replace power transistor
module.
Replace inverter PCB.
Replace power transistor
module.
Refer Page 63.
(Remove the power cable
from compressor and check
the resistance between P-U,
P-V, P-W, N-U, N-V, N-W
respectively.
Replace inverter PCB.
2. Error detection method
When anomalously high output
current of inverter is detected
by the current sensormounted in
the power transistor
3. Condition of error displayed
When 88A or higher output
current of inverter is detected 4
times within 15 minutes.
4. Presumable cause
• Compressor anomaly
• Leakage of refrigerant
• Power transistor module
anomaly
• Anomalous power source for
inverter PCB
• Outdoor fan motor anomaly
Note:
In case that there is no the insulation resistance anomaly, the compressor anomaly could be considered.
If this anomaly occurs after replacement of power transistor module and/or inverter PCB, try to replace compressor as well.
If the error does not recur, connect the Mente PC and continue to collect data
YES